Honeywell Home Security System Ademco Vista Series Commercial Burglary Partitioned Security System With Scheduling User Manual

$'(0&2ꢀ9,67$ꢀ6(5,(6ꢀ  
9,67$ꢁꢂꢃ3ꢄ9,67$ꢁꢂꢃ38/ꢀ  
&RPPHUFLDOꢀ%XUJODU\ꢀ  
3DUWLWLRQHGꢀ6HFXULW\ꢀ6\VWHPꢀ  
:LWKꢀ6FKHGXOLQJꢀ  
3URJUDPPLQJ *XLGH  
VISTA50P-PRV2 5/04 Rev A  
 
Recommended Programming Procedure  
The following is a step-by-step procedure recommended for programming your VISTA-50P/VISTA-50PUL system.  
1. Set the keypads (and other peripheral devices) to the appropriate addresses.  
2. Set factory defaults by pressing 97.  
This will automatically enable keypad addresses 00-03, so be sure at least one keypad is set to one of these  
addresses.  
3. Program system-wide (global) data fields.  
Using the programming form as a guide, enter program mode and program all system-wide programming  
fields. These options affect the entire system, regardless of partitions. They include control options,  
downloader and dialer options, RF options, event logging options, etc. Refer to the Program Field Index for a  
listing of the program fields and their function.  
Note that field 200 (number of partitions) must be programmed before continuing.  
4. Program partition-specific fields.  
When the system-wide fields have been programmed, program all partition-specific programming fields by  
first pressing 91 to select a partition (while still in data field program mode). Then enter the first partition-  
specific field number 09. When you are finished, the next partition-specific field is automatically displayed.  
Partition-specific fields can have different values for each partition. To program the fields for the next partition,  
press 91, enter the desired partition number, then enter field 09. Refer to the PROGRAMMING section in  
the ADEMCO VISTA-50P/VISTA-50PUL Installation and Setup Guide for detailed instructions.  
5. Use #93 Menu Mode for device programming.  
Refer to Device Programming in this guide to assign keypad ID numbers and default partitions for each  
keypad, and to selectively suppress certain keypad sounding options. Also use this mode to assign RF  
receivers, relay modules, the VIP module, the ECP Long Range Radio, and the VISTA Gateway Module.  
6. Use #93 Menu Mode for zone programming.  
Refer to Zone Programming in this guide to program zone response types, assign right loop zones and  
wireless zones, assign zones to partitions, and to program alarm report codes.  
7. Use #93 Menu Mode for programming outputs.  
Refer to Output Programming in this guide to program desired output operation.  
8. Program Communication options.  
Refer to System Communication section in the ADEMCO VISTA-50P/VISTA-50PUL Installation and Setup  
Guide for detailed instructions. Then use #93 menu mode to program report codes.  
9. Use #93 Menu Mode for programming alpha descriptors.  
Refer to Alpha Programming in this guide to enter zone and partition descriptors and a custom installer’s  
message.  
10. Use #93 Menu Mode for relay voice descriptors and custom word substitutes.  
Refer to Relay Voice Descriptors in this guide for further instructions for programming relay descriptors to be  
annunciated by the VIP module, as well as the Custom Index section for custom word substitutes.  
11. Use #80 Mode for programming schedules.  
Refer to the Scheduling Menu Prompts in the ADEMCO VISTA-50P/VISTA-50PUL Installation and Setup  
Guide to program open/close schedules, temporary and holiday schedules, limitation of access schedules,  
and time-driven events.  
12. Define user access codes.  
Refer to User Access Codes in the ADEMCO VISTA-50P/VISTA-50PUL Installation and Setup Guide to  
program authority level, O/C reporting option, partition assignments, and RF key assignments for each user.  
13. Exit Programming Mode.  
Exit programming mode by pressing either 98 or 99. Additional entries of 99 are required if the exit is  
being done from fields 100 and above.  
To prevent re-access to programming mode using the Installer’s code, use 98. The only way to re-access  
programming mode is by depressing both the [] and [#] keys at the same time within 30 seconds of power-  
up.  
Exiting by using 99 always allows reentry into programming mode using the Installer code. Either way of  
exiting allows access via downloading. Note that if local programming lockout is set via downloading,  
programming mode cannot be entered at the keypad.  
3 –  
 
Program Field Index  
On the following pages, the programming fields have been arranged in numerical order. Use this index to cross-reference the  
fields on the programming form.  
Field  
Group  
Field Group  
Field Group  
System-Wide  
*00  
*02  
*03  
*04  
*05  
*09  
*10  
*11  
*12  
*13  
*14  
*15  
*16  
*17  
*19  
*20  
*21  
*22  
*23  
*24  
*25  
*26  
*27  
*28  
*29  
*30  
*31  
*32  
*33  
*34  
*35  
*36  
*37  
*38  
*39  
*40  
*41  
*42  
*43  
*44  
*45  
*46  
*47  
*48  
*49  
*50  
*51  
*52  
*53  
*54  
*56  
System-Wide  
*57  
Communications  
1*28  
1*29  
1*30  
1*31  
1*33  
1*34  
1*35  
1*36  
1*37  
1*38  
1*39  
1*40  
1*41  
1*42  
1*43  
1*44  
1*45  
1*46  
1*47  
1*48  
1*49  
1*52  
1*53  
1*57  
1*58  
1*60  
1*70  
1*71  
1*72  
1*73  
1*74  
1*75  
1*76  
2*00  
2*01  
2*02  
2*05  
2*06  
2*07  
2*08  
2*09  
2*10  
2*11  
2*13  
2*14  
2*18  
2*19  
2*20  
2*21  
# 93 Menu Mode  
# 93 Menu Mode  
# 93 Menu Mode  
# 93 Menu Mode  
Partition-Specific  
Partition-Specific  
Partition-Specific  
Partition-Specific  
Partition-Specific  
System-Wide  
System-Wide  
Partition-Specific  
System-Wide  
System-Wide  
System-Wide  
System-Wide  
Partition-Specific  
Partition-Specific  
System-Wide  
*58  
*59  
*60  
*61  
*62  
*63  
*64  
*65  
*66  
*67  
*68  
*69  
*70  
*71  
*72  
*73  
*74  
*75  
*76  
*77  
*78  
*79  
*80  
*81  
*82  
*83  
*84  
*85  
*87  
*88  
*89  
*90  
1*01  
1*02  
1*03  
1*04  
1*05  
1*06  
1*07  
1*08  
1*09  
1*17  
1*18  
1*19  
1*20  
1*21  
1*22  
1*23  
1*24  
1*25  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Partition-Specific  
Partition-Specific  
Partition-Specific  
Partition-Specific  
Communications  
Partition-Specific  
# 93 Menu Mode  
# 93 Menu Mode  
# 93 Menu Mode  
# 93 Menu Mode  
# 93 Menu Mode  
# 93 Menu Mode  
# 93 Menu Mode  
# 93 Menu Mode  
# 93 Menu Mode  
System-Wide  
System-Wide  
System-Wide  
System-Wide  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Partition-Specific  
System-Wide  
Partition-Specific  
System-Wide  
Partition-Specific  
System-Wide  
System-Wide  
Partition-Specific  
System-Wide  
System-Wide  
System-Wide  
System-Wide  
System-Wide  
System-Wide  
System-Wide  
System-Wide  
System-Wide  
System-Wide  
Partition-Specific  
System-Wide  
System-Wide  
System-Wide  
Partition-Specific  
Partition-Specific  
Partition-Specific  
Partition-Specific  
Partition-Specific  
Partition-Specific  
System-Wide  
Communications  
Communications  
Partition-Specific  
System-Wide  
System-Wide  
Communications  
Communications  
System-Wide  
Partition-Specific  
Communications  
Communications  
Partition-Specific  
Communications  
Communications  
System-Wide  
System-Wide  
System-Wide  
Partition-Specific  
Partition-Specific  
Communications  
System-Wide  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
Communications  
System-Wide  
Partition-Specific  
Partition-Specific  
System-Wide  
System-Wide  
System-Wide  
System-Wide  
System-Wide  
System-Wide  
Partition-Specific  
System-Wide  
Communications  
4 –  
 
VISTA-50P/VISTA-50PUL Programming Form  
Some fields are programmed for each partition (shown as shaded fields). If you are programming a multiple-partition system,  
see the Partition-Specific Fields section for programming these fields. Standard default (*97) values are shown in brackets [ ].  
*00 INSTALLER CODE  
| | |  
*25 BURG.TRIGGER FOR RESPONSE TYPE 8 [1]  
Enter 4 digits, 0-9 [4140]  
1=enable; 0=disable  
*02 *05 RESPONSE TYPES FOR ZONES  
*26 INTELLIGENT TEST REPORTING  
[0]  
Skip these fields. Use #93 Menu Mode, Zone  
Programming to program the response types.  
1=yes (no report sent if any other report was recently sent);  
0=no (send report at programmed interval, field *27)  
Must be 0 for UL installations.  
*09 ENTRY DELAY #1  
[02]  
[03]  
[06]  
|
|
|
00, 02-15 times 15 seconds  
Maximum "03" for UL.  
*27 TEST REPORT INTERVAL  
[024]  
| | |  
Enter interval in hours, 001-999; 0000=no report;  
Max. 024 for UL installations.  
*10 EXIT DELAY #1  
00, 03-15 times 15 seconds  
Maximum "04" for UL installations.  
*28 POWER UP IN PREVIOUS STATE  
[1]  
1=yes; 0=no; "1" for UL installations.  
*11 ENTRY DELAY #2  
*29 QUICK ARM  
[1]  
00, 02-15 times 15 seconds (must be longer than Entry Delay  
#1). Maximum "03" for UL installations.  
1=yes; 0=no  
*30 TOUCHTONE OR ROTARY DIAL  
[0]  
*12 EXIT DELAY #2  
[08]  
|
1=TouchTone; 0=rotary  
00, 03-15 times 15 seconds (must be longer than Exit Delay  
#1). Maximum "04" for UL installations.  
*31 PABX ACCESS CODE  
|
|
|
|
|
|
|
|
*13 ALARM SOUNDER DURATION  
[04]  
|
00-09; B-F (11-15)  
01-15 times 2 minutes. Must be minimum 16 minutes for UL  
installations.  
*32 PRIM. SUBS. ACCT #  
Enter 00-09; B-F (11-15) [15 15 15 15]  
*33 PRIMARY PHONE NUMBER  
*14 ZONE 9 RESPONSE TIME  
[0]  
Enter 1 for fast response time 10ms  
Enter 0 for normal response time 350ms.  
Must be 0 for UL installations.  
*15 KEYSWITCH ASSIGNMENT  
[0]  
[0]  
Enter 0-9 for each digit. Enter #11 for *, #12 for #,  
#13 for 2 second pause  
*34 SECONDARY PHONE NUMBER  
Enter partition in which keyswitch used,  
1-8; 0=disable  
*16 CONFIRMATION OF ARMING DING  
1=enable; 0=disable.  
Must be "1" for UL Installations.  
*17 AC LOSS KEYPAD SOUNDING  
[0]  
[0]  
Enter 0-9 for each digit. Enter #11 for *, #12 for #,  
#13 for 2 second pause  
*35 DOWNLOAD PHONE NO.  
1=yes; 0=no  
*19 RANDOMIZE AC LOSS REPORT  
1=10-40 min; 0=normal report (about 2 min. after AC loss).  
*20 VIP MODULE PHONE CODE  
|
|
Enter 0-9 for each digit. Enter #11 for *, #12 for #,  
#13 for 2 second pause  
*36 DOWNLOAD ID NO.  
Enter 01 - 09 for the first digit; enter  
11 for *or 12 for #for the second digit.  
Must be set to "0" for UL installations.  
[00],  
[11]  
|
|
|
|
|
|
|
|
*21 PREVENT FIRE TIMEOUT  
[0]  
Enter 00-09; A-F (10-15) [15 15 15 15 15 15 15 15]  
1=No timeout; 0=Timeout.  
*37 DOWNLOAD COMMAND ENABLES  
*22 KEYPAD PANIC ENABLES  
[001]  
0
1=enable; 0=disable  
995 996 999  
Dlr ShtdwnSys ShtdwnNot UsedRmt BypRmt DisarmRmt ArmUpld PgmDwnld Pgm  
See field 1*53 for Callback disable option; [1=enable];  
0=disable. For UL installations, all entries must be "0."  
*23 MULTIPLE ALARMS  
[1]  
1=yes; 0=no  
*38 PREVENT ZONE XX BYPASS  
[00]  
|
*24 IGNORE EXPANSION ZONE TAMPER  
[0]  
01-86; 00 if all zones (except fire zones) can be bypassed  
1=Ignore; 0=Enable tamper for RF and RPMs.  
Must be "0" for UL installations if using these devices.  
5 –  
 
*58 SUPERVISORY AND RESTORE CODES FOR ZONES  
*39 ENABLE OPEN/CLOSE REPORT FOR  
[0]  
01-16. Enter 00-09; B-F (11-15). Default = [00 00 00 00 00]  
INSTALLER CODE 1=enable; 0=disable  
|
|
Trbl  
|
|
Byp  
|
*40 OPEN/CLOSE REPORT FOR KEYSWITCH [0]  
Alarm Rst  
Trbl Rst  
Byp Rst  
1=enable; 0=disable  
*59 *62 ALARM REPORT CODES & ID DIGITS FOR  
ZONES 17-32.  
*41 NORMALLY CLOSED or EOLR (Zones 2-8) [1]  
Skip these fields. Use #93 Menu Mode, Zone  
Programming to program the report codes.  
1=N.C.loops; 0=EOLR supervision.  
Must be "0" for UL installations.  
*63 SUPERVISORY AND RESTORE CODES FOR ZONES  
17-32. Enter 00-09; B-F (11-15). Default = [00 00 00 00 00]  
*42 DIAL TONE PAUSE  
[0]  
[1]  
|
|
|
|
|
0=5 seconds; 1=11 seconds; 2=30 seconds.  
Must be "0" UL Installations.  
Alarm Rst  
Trbl  
Trbl Rst  
Byp  
Byp Rst  
*64 *67 ALARM REPORT CODES & ID DIGITS FOR  
*43 DIAL TONE DETECTION  
ZONES 33-48.  
1=wait for true dial tone; 0=pause, then dial  
Skip these fields. Use #93 Menu Mode, Zone  
Programming to program the report codes.  
*44 RING DETECTION COUNT  
[00]  
|
*68 SUPERVISORY AND RESTORE CODES FOR ZONES  
01-14; 15=answering machine; 00=no detection.  
Must be "00" for UL Burglary.  
33-48. Enter 00-09; B-F (11-15). Default = [00 00 00 00 00]  
|
|
Trbl  
|
|
Byp  
|
*45 PRIMARY FORMAT  
[1]  
Alarm Rst  
Trbl Rst  
Byp Rst  
0=Low Speed; 1=Contact ID; 2=ADEMCO High Speed;  
3= ADEMCO Express  
*69 *72 ALARM REPORT CODES & ID DIGITS FOR  
ZONES 49-64.  
*46 LOW SPEED FORMAT (Primary)  
[0]  
Skip these fields. Use #93 Menu Mode, Zone  
Programming to program the report codes.  
0= ADEMCO Low Speed; 1=Sescoa/Radionics  
*73 SUPERVISORY AND RESTORE CODES FOR ZONES  
*47 SECONDARY FORMAT  
[1]  
49-64. Enter 00-09; B-F (11-15). Default = [00 00 00 00 00]  
0=Low Speed; 1=Contact ID; 2= ADEMCO High Speed;  
3= ADEMCO Express  
|
|
|
|
|
Alarm Rst  
Trbl  
Trbl Rst  
Byp  
Byp Rst  
*48 LOW SPEED FORMAT (Sec.)  
[0]  
*74 *77 ALARM REPORT CODES & ID DIGITS FOR  
0= ADEMCO Low Speed; 1=Sescoa/Radionics  
ZONES 81-99.  
Skip these fields. Use #93 Menu Mode, Zone  
Programming to program the report codes.  
*49 CHECKSUM VERIFICATION  
[0] [0]  
1=yes; 0=no  
Prim  
Sec  
*78 SUPERVISORY AND RESTORE CODES FOR ZONES  
81-99. Enter 00-09; B-F (11-15). Default = [00 00 00 00 00]  
*50 SESCOA/RADIONICS SELECT  
[0]  
[0]  
|
|
|
|
|
1=Sescoa; 0=Radionics  
Alarm Rst  
Trbl  
Trbl Rst  
Byp  
Byp Rst  
*51 DUAL REPORTING  
ZONE TYPE RESTORE ENABLES  
1=yes; 0=no If used with Spilt Reporting "1" option (1*34),  
alarms and alarm restores go to both primary & secondary  
numbers, while all other reports go to secondary only. If used  
with Split Reporting "2" option, alarms and alarm restores go to  
both, open/close and test messages go to secondary only,  
while all other reports go to primary.  
*79 FOR ZONE TYPES 1-8  
1
2
3
4
5
6
7
8
1=enable; [0=disable]  
*52 STANDARD/EXPANDED REPORT FOR PRIMARY  
*80 FOR TYPES 9, and 10  
[0 0 0 0 0 0]  
9
10  
Alarm Rstr Byp Trbl O/C LoBat  
0=standard; 1=expanded;  
1=enable; [0=disable]  
Note: Expanded overrides 4+2 format.  
*53 STANDARD/EXPANDED REPORT FOR SECONDARY  
[0 0 0 0 0 0]  
Alarm Rstr Byp Trbl O/C LoBat  
0=standard; 1=expanded;  
*54 *57 ALARM REPORT CODES & ID DIGITS FOR  
ZONES 01-16.  
Skip these fields. Use #93 Menu Mode, Zone  
Programming to program the report codes.  
6 –  
 
*80 *81  
SYSTEM NON-ALARM CODES  
Enter 00-09; B-F (11-15).  
Default = 00 for all reports  
*80 1st Digit  
1*20 EXIT ERROR LOGIC ENABLE  
[0]  
0=No; 1=Bypass E/E and Interior zones faulted after exit  
delay.  
*81 2nd Digit  
Must be "0" for UL installations.  
|
|
Close  
1*21 EXIT DELAY RESET  
[0]  
|
|
|
Open  
0=No; 1=Resets Exit Delay to programmed value after zone  
is closed and then faulted prior to end of exit delay.  
Must be "0" for UL installations.  
|
Low Battery  
FIELDS 122-125: Allow four sets of two zones each to be  
linked so that both must fault within a five minute period to  
cause an alarm. Default for these fields = [000], [000].  
|
|
Low Battery Restore  
|
|
AC Loss  
|
|
|
|
|
|
|
|
1*22 CROSS-ZONING PAIR ONE  
1*23 CROSS-ZONING PAIR TWO  
1*24 CROSS-ZONING PAIR THREE  
|
|
AC Restore  
|
|
Test  
|
|
Power Up  
1*25 CROSS-ZONING PAIR FOUR  
|
|
Cancel  
MISCELLANEOUS WIRELESS OPTIONS  
Fields 1*28 - 1*31 are not applicable for UL installations.  
|
|
Program Tamper  
1*28 RF TX LOW BATTERY SOUND  
[0]  
*83 FIRST TEST REPORT TIME  
|
|
|
1=immediate; 0=when disarmed  
[Day 00; hour 12; min 00] Days 01-07 Hours 00-23 Min 00-  
59; 00 in all boxes = instant (Day 01= Monday)  
1*29 RF TX LOW BATTERY REPORTING  
[0]  
1=enable; 0=disable  
*84 SWINGER SUPPRESSION  
[01]  
|
1*30 RF RCVR CHECK-IN INTERVAL  
[06]  
[12]  
|
|
01-15 alarms  
Must be "00" (disabled) for UL.  
*85 ENABLE DIALER REPORTS FOR PANICS & DURESS  
02-15 times 2 hours; 00 disables supervision  
1*31 RF XMITTER CHECK-IN INTERVAL  
02-15 times 2 hours; 00 disables transmitter supervision  
1=enable; [0=disable]  
995 996 999 Duress  
1*33 TOUCHTONE W/ROTARY BACKUP  
[0]  
*87 ENTRY WARNING  
[1]  
1=enable; 0=disable  
1=continuous; 0=3 beeps  
1*34 COMM. SPLIT REPORTING  
[0]  
*88 BURG. ALARM COMM. DELAY  
[0]  
0=no; 1=alarms and alarm restores primary, others secondary;  
2=open/close, test secondary, others primary. See 51 for  
comments if using with dual reporting.  
1=16 seconds; 0=no delay  
Must be "0" for UL installations.  
1*35 1*38 ALARM REPORT CODES & ID DIGITS FOR  
ZONES 65-80.  
*89 RESTORE REPORT TIMING  
[0]  
0=Instant; 1=After bell timeout if zone is restored; 2=when  
system is disarmed. Must be "0" for UL installations.  
Skip these fields. Use #93 Menu Mode, Zone  
Programming to program the report codes.  
1*39 SUPERVISORY AND RESTORE CODES FOR  
ZONES 65-80. Enter 00-09; B-F (11-15).  
Default = [00 00 00 00 00]  
*90 SEC. SUBS. ACCT #  
Enter 00-09; B-F (11-15) [15 15 15 15]  
2nd Page Programming Fields (press *94)  
|
|
|
|
|
|
|
|
|
1*01 1*09 ASSIGN RESPONSE TYPE FOR ZONES.  
Skip these fields. Use #93 Menu Mode, Zone  
Alarm Rst  
Trbl  
Trbl Rst  
Byp  
Byp Rst  
Programming to program the response types.  
1*17 LOBBY PARTITION  
[0]  
Enter the "common lobby" partition (1-8)  
1*18 AFFECTS LOBBY  
[0]  
Enter 1 if this partition affects the common lobby; enter 0 if it  
does not.  
Must be "0" for UL installations.  
1*19 ARMS LOBBY  
[0]  
Enter 1 if arming this partition attempts to arm lobby; enter 0  
if it does not.  
Must be "0" for UL installations.  
7 –  
 
1*40 1*41 NON-ALARM DIALER CODES  
Enter 00-09; B-F (11-15).  
1*58 5800 RF BUTTON FORCE ARM  
[0]  
Default = 00 for all reports  
Enter "1" to enable. If a zone is faulted after pressing button,  
keypad will beep once. Pressing the button again within 4  
sec. bypasses the zone. Enter "0" to disable.  
Must be "0" for UL installations.  
1*40 1st Digit  
1*41 2nd Digit  
|
|
Armed STAY  
1*60 ZONE 5 AUDIO ALARM VERIFICATION  
[0]  
|
|
Time/Date Set or Event Log Reset  
Enter 1 If 2-way audio (AAV) is being used; Enter 0 if it is  
not.  
|
|
Event Log 50% & 90% Full  
Must be "0" for UL installations.  
|
|
Event Log Overflow  
1*69 PRINTER TYPE  
[0]  
Enter 0 if you are using a parallel printer connected to the  
VA8201 Alpha Pager Module.  
|
|
Exit Error (Zone)  
Enter 1 if you are using a serial printer.  
1*70 EVENT LOG TYPES  
|
|
|
Exit Error (User)  
|
Recent Close  
[1 0 0 0 1]  
Alarm Chk Byp O/C Syst  
1=enable; 0=disable  
1*42 CALL WAITING DEFEAT  
[0]  
1=Yes; 0=No  
1*71 12/24 HOUR TIME STAMP FORMAT  
[0]  
0=12 hour; 1=24 hour  
1*43 PERM. KEYPAD BACKLIGHT  
[0]  
1=enable; 0=disable When disabled, display lights when any  
key is pressed, and turns off after period of keypad inactivity.  
1*72 EVENT LOG PRINTER ON-LINE  
[0]  
0=disable; 1=enable  
1*44 WIRELESS KEYPAD TAMPER  
[0]  
1*73 PRINTER BAUD RATE  
[0]  
DETECTION  
1=enable; 0=disable.  
Must be "0" for UL installations.  
1=300; 0=1200  
1*74 RELAY TIMEOUT XXX MINUTES [000]  
| |  
1*45 EXIT DELAY SOUNDING  
[0]  
Enter the relay timeout, 000-127 in multiples of 2 minutes,  
desired for #80 Menu Mode time-driven event relay  
command numbers "04/09" and #93 Menu Mode Output  
Programming output command "56."  
1=enable; 0=disable. Produces quick beeping during exit  
delay if enabled.  
1*46 AUXILIARY OUTPUT MODE  
Enter 0 for ground start output.  
[0]  
1*75 RELAY TIMEOUT YYY SECONDS [000]  
| |  
Enter the relay timeout, 000-127 seconds, desired for #80  
Menu Mode time driven event relay command numbers  
"05/10" and #93 Menu Mode Output Programming command  
"57."  
Enter 1 for open/close trigger (is produced only if all partitions  
are armed.  
Enter 2 for keypad-like sounding. Applies to the partition  
enabled in field *15.  
Enter 3 if AAV module is being used.  
NOTE: Only one of the above options may be active within  
the system.  
1*76 ACCESS CONTROL RELAY  
[00]  
|
Relay will be pulsed for 2 seconds whenever code + [0] is  
pressed. Enter 00-16; 00=none.  
Must be "00" for UL.  
1*47 CHIME ON EXTERNAL SIREN  
[0]  
1=enable; 0=disable  
3rd Page Programming Fields (press *94)  
1*48 WIRELESS KEYPAD ASSIGNMENT  
[0]  
2*00 NUMBER OF PARTITIONS  
[1]  
0=disable; enter partition in which RF keypad used, 1-8.  
Must be "0" for UL installations.  
Enter 1-8  
2*01 DAYLIGHT SAVING TIME [04, 10]  
|
|
1*49 SUPPRESS TX SUPERVISION SOUND  
[1]  
START/END MONTH  
00-12; if no daylight saving time, enter 00,00  
Start End  
1=disable; 0=enable.  
Must be "0" for UL installations.  
2*02 DAYLIGHT SAVING TIME  
[1, 5]  
|
1*52 SEND CANCEL IF ALARM + OFF  
[1]  
[0]  
1=no restriction; 0=within bell timeout period only  
START/END WEEKEND  
Enter 1-7. 1=first; 2=second; 3=third; 4=fourth; 5=last;  
6=next to last; 7=3rd from last [1,5]  
Start | End  
1*53 DOWNLOAD CALLBACK  
1=callback not required; 0=callback required.  
Must be "0" for UL installations.  
2*05 AUTO-ARM DELAY  
[15]  
|
Enter the time between the end of the arming window and  
the start of auto-arming warning period, in values of 1-14  
times 4 minutes 00=instant; [15=no auto arm at all]. When  
this delay expires, the Auto-Arm Warning Period begins.  
1*57 5800 RF BUTTON GLOBAL ARM  
[0]  
1=enable; 0=disable  
8 –  
 
2*06 AUTO-ARM WARNING PERIOD  
[15]  
|
2*18 ENABLE GOTO FOR THIS PARTITION  
[0]  
[0]  
This is the time during which the user is warned to exit the  
premises prior to the auto-arming of the system (beeps every  
15 seconds; "ALERT" displayed). Enter 01-15 minutes.  
00=instant at end of arming delay.  
1=Allow log-on from other partitions; 0=disable  
2*19 USE PARTITION DESCRIPTORS  
0=disable; 1=enable  
2*07 AUTO-DISARM DELAY  
[15]  
|
2*20 ENABLE J7 TRIGGERS FOR PARTITION [1]  
This is the time between the end of the disarming window  
and the start of auto-disarming. Enter 01-14 times 4 minutes;  
00=instant at end of window; 15=no auto-disarm.  
0=disable for displayed partition; 1=enable for displayed  
partition  
2*21 ENABLE SUPERVISION PULSES FOR LRR  
2*08 ENABLE FORCE ARM FOR AUTO-ARM  
[0]  
TRIGGER OUTPUTS  
[000]  
| |  
0=disable; 1=enable  
Used for supervised connection to 7920SE.  
F
B
P
2*09 OPEN/CLOSE REPORTS BY EXCEPTION [0]  
Enter 0 to disable or 1 to enable the listed outputs.  
F= Fire; B= Burglary; P= Silent Panic/Duress.  
Must be 1 for UL. Installations.  
1=enable; 0=disable  
If enabled, only openings and closings occurring outside the  
scheduled opening/closing windows will trigger dialer  
reports. Opening reports will also be suppressed during the  
closing window, in order to prevent false reports when the  
user arms the system and then reenters the premises to  
retrieve a forgotten item.  
SUMMARY OF PROGRAMMING COMMANDS  
To enter program mode, enter installer code + [8] + [0] +  
[0]  
2*10 ALLOW DISARMING ONLY DURING  
[0]  
ARMING/DISARMING WINDOWS  
0=disable; 1=enable  
See system-wide field 2*11 if enabling field 2*10. This  
feature adds high security to the installation.  
To set standard defaults, press *97  
To change to next page of program fields, press *94  
To return to previous set of fields, press *99  
To erase account and phone number field entries,  
press [*] + field number + [*]  
2*11 ALLOW DISARM OUTSIDE WINDOW  
[0]  
To assign zone descriptors, press #93 + follow menu  
prompts  
IF ALARM OCCURS  
Used only if field 2*10 (partition-specific field) is set to "1." If  
this field is enabled ("1") the system can be disarmed outside  
the disarm window if an alarm has occurred. If "0," disarming  
can only be done during the disarm window. If field 2*10 is  
set to "0" for a partition, this field has no effect for that  
partition.  
To add custom words, press #93 + follow menu prompts  
To enter Installer's Message, press #93 + follow menu  
prompts  
To exit program mode, enter *99 OR *98: *99 allows re-  
access to programming mode by installer code. *98  
prevents re-access to programming mode by installer  
code.  
2*13 2*14 SCHEDULING RELATED REPORT CODES  
Enter 00-09; B-F (11-15).  
Default = 00 for all reports  
2*13 1st Digit  
2*14 2nd Digit  
|
|
Early Opening  
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Early Closing  
Late Opening  
Late Closing  
No Opening (late to open)  
No Closing (late to close)  
Auto-Arm Failure  
Access Schedule Changed  
9 –  
 
Partition-Specific Fields  
(Duplicate this page for each partition in the installation.)  
To program these fields,  
1. Press *91 to select a partition.  
2. Enter a partition-specific field number (ex. *09).  
3. Make the required entry.  
4. Repeat steps 1-3 for each partition in the system.  
PARTITION #____ PROGRAM FIELDS  
1st Page Fields  
*87 ENTRY WARNING  
[1]  
[0]  
1=continuous; 0=3 beeps  
*09 ENTRY DELAY #1  
[02]  
[03]  
[06]  
[08]  
[04]  
|
|
|
|
|
00, 02-15 times 15 seconds.  
Maximum 03 for UL Listed installations.  
*88 BURG. ALARM COMM. DELAY  
1=16 seconds; 0=no delay.  
Must be "0" for UL installations. Must be 1for SIA  
installations.  
*10 EXIT DELAY #1  
00, 03-15 times 15 seconds.  
Maximum 04 for UL Listed installations.  
*90 SEC. SUBS. ACCT #  
|
|
|
|
Enter 00-09; B-F (11-15) [15 15 15 15]  
*11 ENTRY DELAY #2  
00, 02-15 times 15 seconds.  
Maximum 03 for UL installations.  
2nd Page Programming Fields (press *94)  
1*18 AFFECTS LOBBY  
[0]  
*12 EXIT DELAY #2  
Enter 1 if this partition affects the common lobby; enter 0 if it  
does not.  
00, 03-15 times 15 seconds.  
Maximum 04 for UL installations.  
1*19 ARMS LOBBY  
[0]  
*13 ALARM SOUNDER DURATION  
Enter 1 if arming this partition attempts to arm lobby; enter 0  
if it does not  
01-15 times 2 minutes.  
Must be minimum 16 minutes for UL installations.  
1*20 EXIT ERROR LOGIC ENABLE  
[0]  
*16 CONFIRMATION OF ARMING DING  
[0]  
0=No; 1=Bypass E/E and Interior zones faulted after exit  
delay.  
Must be "0" for UL installations.  
1=enable; 0=disable.  
Must be "1" for UL installations.  
*22 KEYPAD PANIC ENABLES  
[001]  
1*21 EXIT DELAY RESET  
[0]  
1=enable; 0=disable  
995 996 999  
[1]  
0=No; 1=Resets Exit Delay to programmed value after zone  
is closed and then faulted prior to end of exit delay.  
Must be "0" for UL installations.  
*23 MULTIPLE ALARMS  
1=yes; 0=no.  
Must be 1 for UL installations.  
1*43 PERM. KEYPAD BACKLIGHT  
[0]  
1=enable; 0=disable. When disabled, display lights when  
any key is pressed, and turns off after period of keypad  
inactivity.  
*29 QUICK ARM  
[1]  
1=yes; 0=no  
*32 PRIM. SUBS. ACCT #  
|
|
|
|
1*45 EXIT DELAY SOUNDING  
[0]  
Enter 00-09; B-F (11-15) [15 15 15 15]  
1=enable; 0=disable. Produces quick beeping during exit  
delay if enabled.  
*38 PREVENT ZONE XX BYPASS  
[00]  
|
1*47 CHIME ON EXTERNAL SIREN  
[0]  
01-86; 000 if all zones (except fire zones) can be bypassed  
1=enable; 0=disable  
*39 ENABLE OPEN/CLOSE REPORT  
[0]  
FOR INSTALLER CODE  
1=enable; 0=disable  
1*52 SEND CANCEL IF ALARM + OFF  
[1]  
1=no restriction; 0=within Bell Timeout period only  
*84 SWINGER SUPPRESSION  
[01]  
|
1*76 ACCESS CONTROL RELAY FOR PART.[00]  
|
01-15 alarms;  
Must be "00" (disabled) for UL installations..  
*85 ENABLE DIALER REPORTS FOR PANICS & DURESS  
Relay will be pulsed for 2 seconds whenever code + [0] is  
pressed. Enter 00-16; 00=none.  
Must be "00" for UL installations.  
1=enable; [0=disable]  
995 996 999 Duress  
10 –  
 
3rd Page Programming Fields (press *94)  
2*18 ENABLE GOTO FOR THIS PARTITION  
[0]  
[1]  
1=Allow log-on from other partitions; 0=disable  
2*05 AUTO-ARM DELAY  
[15]  
|
Enter the time between the end of the arming window and  
the start of auto-arming warning period, in values of 1-14  
times 4 minutes 00=instant; [15=no auto arm at all]. When  
this delay expires, the Auto-Arm Warning Period begins.  
2*20 ENABLE J7 TRIGGERS BY PARTITION  
0=disable for displayed partition; 1=enable for displayed  
partition  
2*06 AUTO-ARM WARNING PERIOD  
[15]  
|
This is the time during which the user is warned to exit the  
premises prior to the auto-arming of the system (beeps  
every 15 seconds; "ALERT" displayed). Enter 01-15 minutes.  
00=instant at end of arming delay .  
SUMMARY OF PROGRAMMING COMMANDS  
To enter program mode, enter installer code + [8] + [0] +  
[0]  
2*07 AUTO-DISARM DELAY  
[15]  
|
To set standard defaults, press *97  
To change to next page of program fields, press *94  
To return to previous set of fields, press *99  
To erase account and phone number field entries,  
press [*] + field number + [*]  
This is the time between the end of the disarming window  
and the start of auto-disarming. Enter 01-14 times 4 minutes;  
00=instant at end of window; 15=no auto-disarm  
2*08 ENABLE FORCE ARM FOR AUTO-ARM  
[0]  
To assign zone descriptors, press #93 + follow menu  
prompts  
To add custom words, press #93 + follow menu prompts  
To enter Installer's Message, press #93 + follow menu  
prompts  
To exit program mode, enter *99 OR *98: *99 allows re-  
access to programming mode by installer code. *98  
prevents re-access to programming mode by installer  
code.  
0=disable; 1=enable  
2*09 OPEN/CLOSE REPORTS BY EXCEPTION [0]  
1=enable; 0=disable If enabled, only openings and closings  
occurring outside the scheduled opening/closing windows  
will trigger dialer reports. Opening reports will also be  
suppressed during the closing window, in order to prevent  
false reports when the user arms the system and then re-  
enters the premises to retrieve a forgotten item.  
2*10 ALLOW DISARMING ONLY DURING  
[0]  
ARMING/DISARMING WINDOWS  
See system-wide field 2*11 if enabling field 2*10. This  
feature adds high security to the installation.  
0=disable; 1=enable  
11 –  
 
Programming With #93 Menu Mode  
NOTE: The following field should be preset before beginning: 2*00 Number of Partitions. In addition, receivers should  
be programmed via Device programming.  
After programming all system related programming fields in the usual way, press #93 while still in programming mode to  
display the first choice of the menu driven programming functions. Press 0 (NO) or 1 (YES) in response to the displayed menu  
selection. Pressing 0 will display the next choice in sequence.  
#93 MENU MODE KEY COMMANDS  
The following is a list of commands used while in the menu mode.  
#93  
[4]  
[#]  
Enters Menu mode  
Serves as ENTER key. Press to have keypad accept entry.  
Backs up to previous screen.  
0
Press to answer NO  
1
Press to answer YES  
01-09  
00  
All data entries are either 1-digit or 2-digit entries.  
Exits menu mode, back into field programming mode, when entered at the first question for each category.  
Menu selections are as follows:  
PROMPT  
EXPLANATION  
For programming the following:  
ZONE PROG?  
Zone Number  
1 = YES 0 = NO  
0
Zone Response Type  
Partition Number for Zone  
Dialer report code for zone  
Input Device Type for zone (whether RF, polling loop, etc.)  
Enrolling serial numbers of 5800 Series transmitters & serial polling loop devices into the system.  
Same as Zone Programming except:  
EXPERT MODE?  
1 = YES 0 = NO  
Done with a minimum number of keystrokes.  
0
0
Can program wireless keys using pre-defined templates.  
For entering alpha descriptors for the following:  
ALPHA PROG?  
Zone Descriptors  
Installer's Message  
Custom Words  
Partition Descriptors  
Relay Descriptors  
1 = YES 0 = NO  
For defining the following device characteristics for addressable devices, including keypads, RF receivers  
(5881), output relay modules (4204), and 4285/4286 VIP Module:  
DEVICE PROG?  
1 = YES 0 = NO  
0
Device Address  
Device Type  
Keypad Options (incl. partition assignment)  
RF House ID  
For defining output relay functions.  
RELAY PGM?  
1 = YES 0 = NO  
0
0
0
For entering voice descriptors for relays to be used with the 4285/4286 VIP Module.  
For creating custom word substitutes for VIP Module annunciation.  
RLY VOICE DESCR?  
1 = YES 0 = NO  
CUSTOM INDEX ?  
1 = YES 0 = NO  
12 –  
 
Zone Programming  
If using 5800 Series transmitters, do not the install batteries until you are ready to enroll them. After enrolling  
the transmitter, the battery need not be removed. This is to prevent enrolling the wrong serial number.  
PROMPT  
EXPLANATION  
Press 1 to enter ZONE PROGRAMMING mode. The following screens appear. Press [] to display the next  
screen. Press # to display a previous screen.  
ZONE PROG?  
1 = YES 0 = NO  
0
0
This prompt appears once upon entering Zone Programming Mode.  
SET TO CONFIRM?  
1 = YES 0 = NO  
If Yes,Confirmation prompts will be displayed after the devices Serial and Loop numbers have been  
entered later.  
Enter the 2-digit zone number to be programmed, as follows:  
Protection Zones = 0186  
ENTER ZONE NO.  
00 = QUIT  
10  
System Supervisory Zones = 88, 89, 90, 91, 92 (duress), 97 and 98 (bell supervision)  
Keypad Panic Zones = 95, 96, 99  
Zone 10 entered  
Press [] to continue.  
This display appears, showing a summary of the zone's current programming. ZT = Zone Type, P =  
Partition, RC = Report Code, In = the input type of device, and L = the device's loop number to which the  
sensor is connected.  
10 ZT  
00  
P
RC In L  
10 00 1  
1
Some devices can support more than one zone by means of individual loops (for example, 5801, 5804,  
5816, 5817, etc.). If the zone is not programmed, the display appears as shown here. If you are checking a  
zone's programming, and it is programmed satisfactorily, press [#] to back up one step and enter another  
zone number, if desired.  
Press [] to continue.  
Each zone must be assigned a zone type, which defines the way in which the system responds to faults in  
that zone. Refer to the Zone Type Definitions section in the ADEMCO VISTA-50P/VISTA-50PUL Installation  
and Setup Guide for detailed definitions of each zone type. Enter the zone type desired (or change it, if  
necessary). Available zone types are listed below.  
10 ZONE TYPE  
PERIMETER  
03  
Zone number 10 and Zone  
Type 03 entry shown  
00 = Assign for Unused Zones  
01 = Entry/Exit #1, Burglary  
02 = Entry/Exit #2, Burglary  
03 = Perimeter, Burglary  
04 = Interior Follower, Burglary  
05 = Trouble Day/Alarm Night  
06 = 24 Hr. Silent Alarm  
08 = 24 Hr. Auxiliary  
09 = Fire Without Verification  
10 = Interior Delay, Burglary  
20 = ArmSTAY†  
These are special zone  
types used with 5800  
Series Wireless  
Pushbutton Units that  
result in arming the system  
in the STAY or AWAY  
mode, or disarming the  
system, depending on the  
selection made.  
21 = Arm AWAY†  
22 = Disarm†  
23 = No Alarm Response  
(e.g., relay activation)  
07 = 24 Hr. Audible Alarm  
Press [] to continue.  
Enter the partition number (18) you are assigning this zone to.  
Press [] to continue.  
10 Partition  
1
Enter the report code. The report code consists of 2 hexadecimal digits, each in turn consisting of 2  
numerical digits. For example, for a report code of "3C," enter 03 for "3" and 12 for "C."  
(Refer to the System Communication section in the Installation and Setup Guide for more information about  
10 REPORT CODE  
1st 03 2nd 12  
3C  
report codes and reporting formats.)  
Press [] to continue.  
13 –  
 
PROMPT  
EXPLANATION  
Enter the input device type as follows:  
00 = not used  
10 INPUT TYPE  
RF Xmitter  
3
01 = hardwired  
Input types 4 & 5 are  
valid for certain 5800  
Series transmitters only  
(e.g., 5801, 5802, 5802CP  
& 5803).  
03 = supervised RF transmitter (RF type)  
04 = unsupervised RF transmitter (UR type)  
05 = RF button-type transmitter (BR type)  
06 = serial number polling loop device (SL type)  
07 = DIP switch-type polling loop device  
08 = right loop of DIP switch type device  
Right loops refer to the use of the right loop on a 4190WH Zone Expander Module and/or 4278 PIR, which  
allow hardwired devices to be monitored by the polling loop.  
If you are programming hardwired or DIP switch polling loop devices, the summary display appears after  
completing this entry.  
Press [] to continue.  
For Serial Number entry and Loop Number entry, do one of the following:  
a. Transmit two open and close (or close and open) sequences. For a button-type transmitter, press and  
release the button, wait approximately 4 seconds, then press and release the button a second time.  
10 INPUT S/N:  
AXXX-XXXX  
L
1
OR  
b. Manually enter the 7-digit serial number printed on a label on the transmitter, using the Alpha keypad.  
Then press the [] key, the cursor moves to the Lposition. You can edit the loop number, if necessary.  
When the loop number is acceptable, press [].  
OR  
c. Press key [C] to copy the last serial number enrolled (used when programming a transmitter with several  
input loops).  
Press [] to accept.  
The cursor will then move to the Loop column (L) with the previously entered/transmitted serial number  
displayed.  
Enter the loop number (refer to 5800 Series Transmitters Loop Designations below).  
10 INPUT S/N:  
A022-4064  
L
1
To Delete an Existing Serial Number, enter 0in the loop number field. The serial number will change to  
0s.  
If 0was entered in error, simply re-enter the loop number or press [#], and the serial number will return to  
the display.  
Press [] to accept.  
The system will then check for a duplicate serial/loop number combination.  
If a duplicate serial/loop number combination is found, the keypad will emit a single long beep, and display  
the serial number along with a ?for the loop number, allowing you to re-enter the correct loop number.  
If the serial/loop number combination is not a duplicate in the system, a display appears showing the serial  
number and loop number entry.  
10 INPUT S/N:  
A022-4064  
L
1
Press [] to continue.  
14 –  
 
5800 Series Transmitters Loop Designations  
LOOP 3  
LOOP 2  
(REED)  
LOOP 1  
(PRIMARY)  
LOOP 2  
LOOP 1  
LOOP 2  
(AUX. CENTER)  
LOOP 1  
(TERMINALS)  
LOOP  
1
LOOP 3  
LOOP 4  
(AUX. RIGHT)  
ALTERNATE  
POSITION  
FOR LOOP 2  
YOU MUST  
ENROLL THIS  
BUTTON  
5817  
ENROLL AS "RF"  
5816MN  
ENROLL AS "RF"  
5801  
5802MN  
ENROLL AS "UR" OR "RF"  
ENROLL AS "UR" OR "RF"  
LOOP 3  
LOOP 2  
(REED)  
YOU MUST  
ENROLL THIS  
BUTTON  
LOOP  
LOOP 1  
(TERMINALS)  
LOOP 2  
LOOP 1  
2
LOOP 4  
(REED)  
LOOP 2  
LOOP 1  
LOOP 3  
(TERMINALS)  
(INTERNAL  
SHOCK  
YOU MUST  
ENROLL THIS  
BUTTON  
SENSOR)  
LOOP 3  
(TERMINALS)  
LOOP 4  
5819S (WHS & BRS)  
ENROLL AS "RF"  
5819  
ENROLL AS "RF"  
LOOP 1  
LOOP 3  
5804  
ENROLL  
AS "BR"  
• •  
SET  
HOUSE  
CODE  
• •  
5827  
SET HOUSE CODE  
• •  
5827BD  
SET HOUSE CODE  
5804BD  
ENROLL AS "BR"  
LOOP  
1
5809  
ENROLL AS "RF"  
LOOP 2  
(REED)  
LOOP 1  
(MOTION)  
LOOP  
1
(Green)  
(Red)  
(Yellow)  
LOOP 1  
(TERMINALS)  
5808  
ENROLL AS "RF"  
5816  
ENROLL AS "RF"  
5850 (GBD)  
ENROLL AS "RF"  
5890  
ENROLL AS "RF"  
5800_trans_loop-V0  
Note: For information on any transmitter not shown above, refer to the instructions accompanying that transmitter for  
details regarding loop numbers, etc.  
The 5802MN, 5802MN2, 5804, 5804BD, 5814, 5816TEMP, 5819, 5819WHS & BRS, 5827BD,  
and 5850 transmitters are not intended for use in UL installations.  
U
L
PROMPT  
EXPLANATION  
Confirmation Option: This prompt only appears if you answered Yesat the first prompt. The system  
enters a confirmation mode so that the operation of the actual programmed input can be confirmed. Activate  
the loop input or button that corresponds to this zone. At any time during this step, you may press the [] key  
on the keypad to save the serial and loop number combination without confirming.  
XMIT TO CONFIRM  
PRESS TO SKIP  
If the serial number transmitted does not match the serial number entered, a display similar to the one  
at the left appears. If the loop number does not match, it is also displayed.  
If so, activate the loop input or button on the transmitter once again. If a match is not obtained (i.e., summary  
display does not appear), press the [#] key twice and then enter or transmit the correct serial number.  
Entd  
A022-4063  
A022-4064  
1
Rcvd  
If the serial number transmitted does match the serial number entered, the system beeps 3 times and a  
summary display appears, showing that zones programming. Note that an sindicates that a transmitters  
serial number has been enrolled.  
10 ZT P RC In  
03 3C RF 1s  
L
1
Press [] to accept the zone information.  
15 –  
 
PROMPT  
EXPLANATION  
The system now returns to the ENTER ZONE NO.prompt for the next zone.  
When all zones have been programmed, enter 00to quit.  
ENTER ZONE NO.  
00 = QUIT  
11  
After you have enrolled each wireless device, remove ONE of the serial number labels from that device and affix it in  
the appropriate column on the worksheets provided later in this Programming Guide; then enter the other information  
(zone number, zone type, etc.) relevant to that device.  
When you have finished programming all zones, test each using the systems Test Mode. Do not use the  
Transmitter ID Sniffer Mode. The system checks only for transmission of one zone on a particular  
transmitter, NOT the zones assigned to each additional loop, and also does not verify polling loop type  
zones.  
Expert Mode Zone Programming  
Expert mode allows you to program zones using the minimum number of screens and keystrokes.  
Expert Mode Zone Programming does not provide the capability to program some of the zones attributes,  
such as Arm w/Fault, Vent Zone, STAY mode, Auto-STAY, Bypass Group, etc. If you want to program a  
zone for any of these attributes, you must use Zone Programming.  
Enter the Programming mode with [Installer Code] + 8 0 0  
Before programming your zones, do the following:  
1. Program field 200: Number of Partitions.  
2. Enable your RF Receiver in Device Programming menu mode.  
To program your zones, press 93 to display the "ZONE PROG?" prompt. Enter 0(NO) to each prompt until the EXPERT  
MODE?prompt appears.  
PROMPT  
EXPLANATION  
Press 1 to enter Expert mode.  
EXPERT MODE?  
1 = YES 0 = NO  
0
This prompt appears once upon entering Expert Mode.  
SET TO CONFIRM?  
0 = NO 1 = YES  
If you select Yes,Confirmation prompts will be displayed after the devices Serial and Loop numbers have  
been entered later.  
0
A summary display appears, showing zone 1s current programming or default values.  
Zn ZT P RC In  
L
01 03  
1
10 HW  
-
Enter the desired 2-digit zone number and press [].  
Note: If you want to exit the Expert mode, enter 00+ [].  
If an sappears after the loop number, it indicates that the transmitters serial number has been enrolled.  
Use the [D] key to enter and duplicate wireless keys (see Entering Wireless Keyslater)  
Zn ZT  
10 03  
P
RC In  
L
1
10 RF 1s  
16 –  
 
PROMPT  
EXPLANATION  
Enter all zone information except for Loop number, or press Cto copy the zone information on this screen  
from the last saved zone (including Loop).  
Zn ZT  
10 03  
P
RC In  
L
-
1
10 RF  
ZT = Zone Type  
P
= Partition  
RC = Report Code  
In = Input Device Type  
L
= Loop number to which the sensor is connected.  
NOTE: Pressing the [C] copies the zone information from the last saved zone, which includes the  
input type. Verify this information is correct for this zone.  
On this screen:  
Use the [A] key to move to the right.  
Use the [B] key to move to left and to back up to ZTfield.  
Press [] to accept the existing or newly-entered zone information.  
If you entered RF, BR, UR or SL for the Input Type, this screen displays. Otherwise the summary screen for  
the next zone displays.  
Enter the 7-digit serial number, using one of the following methods:  
a. Transmit two open and close (or close and open) sequences. For a button-type transmitter, press and  
release the button, wait approximately 4 seconds, then press and release the button a second time.  
OR  
10 INPUT S/N:  
A XXX-XXXX  
L
-
b. Manually enter the 7-digit serial number printed on a label on the transmitter, using the alpha keypad.  
Then press the [] key, the cursor will move to the Lposition. You can edit the loop number, if  
necessary. When the loop number is acceptable, press [].  
OR  
c. Press key [C] to copy the last serial number enrolled (used when programming a transmitter with several  
input loops).  
Remember, you can use the [A] key to move to the right or the [B] key to move to the left.  
You can also use the [#] key to back up without saving.  
Press [] to accept the serial number and advance to the Lposition (if method aor cwas used), then  
enter the loop number.  
If necessary, press the [#] key to back up without saving, and re-enter or edit the serial number before  
pressing [] to save  
10 INPUT S/N:  
A022-4064  
L
1
The system checks for a duplicate. If a duplicate serial/loop number combination is found, the keypad will  
emit a single long beep, and display the serial number along with a ?for the loop number, allowing you to  
re-enter the correct loop number.  
To Delete an Existing Serial Number, enter 0in the loop number field. The serial number will change to  
0s.  
If 0was entered in error, simply re-enter the loop number or press [#], and the serial number will return to  
10 INPUT S/N:  
A000-0000  
L
1
the display.  
The prompt to confirm appears. This prompt only appears if you answered Yesat the SET TO  
CONFIRM?prompt.  
The system enters a confirmation mode so that the operation of the actual programmed input can be  
confirmed. Activate the loop input or button that corresponds to this zone. At any time during this step, you  
may press the [] key on the keypad to save the serial and loop number combination without confirming.  
XMIT TO CONFIRM  
PRESS TO SKIP  
If the serial number transmitted does not match the serial number entered, a display similar to the one  
at the left appears. If the loop number does not match, it also is displayed.  
If so, activate the loop input or button on the transmitter once again. If a match is not obtained (i.e., summary  
display for the next zone does not appear), press the [#] key twice and then enter or transmit the correct  
serial number.  
Entd  
A022-4063  
A022-4064  
1
Rcvd  
Activate the button on the wireless key again after re-entering the serial number.  
If the serial number transmitted matches the serial number entered, the system beeps 3 times and  
advances to the summary display for the next zone's programming.  
Zn  
11  
ZT  
00  
P
1
RC In  
L
10 00 1  
After all the zones have been programmed, enter 00 for the zone number to quit.  
After you have enrolled each wireless device, remove ONE of the serial number labels from that device and affix it in  
the appropriate column on the worksheets provided later in this Programming Guide; then enter the other information  
(zone number, zone type, etc.) relevant to that device.  
17 –  
 
Entering Wireless Keys  
If you pressed the D key previously to enter defaults for 5804 and/or 5804BD wireless keys, the following screens appear:  
PROMPT  
EXPLANATION  
Enter template number (16).  
FROM TEMPLATE  
13 = 5804 templates; 46 = 5804BD templates. See the defaults provided for each template in the chart  
that follows these procedures.  
16  
1
Select from templates. Press [] to display template (template 1 shown selected).  
Note: If necessary, press [#] to back up and re-enter template number.  
Press [#] if you want to return to zone attributes screen.  
When you press [], the selected template is displayed.  
Top line of display represents loop numbers; bottom line represents zone type.  
Press [] to accept template.  
L
01 02 03 04  
ZT 23 22 21 23  
1
Enter partition number for wireless key.  
PARTITION  
Press [] to continue.  
1
The system searches for the highest available, consecutive 4-zone group (the four zones required for the  
5804 and 5804BD), and displays the lowest zone number of the group.  
If you want to start at a different zone number, enter the zone desired and press [].  
If that zone number is displayed, the system has the required number of consecutive zones available,  
beginning with the zone you entered. If not, the system again displays a suggested zone that can be used.  
If the required number of consecutive zones is not available at all, the system will display 00.”  
Press [] to accept.  
ENTER ZONE NO  
00 = QUIT  
24  
L
Example of zone number  
suggested by the system.  
This indicates that zones  
24, 25, 26, and 27 are  
available.  
To enter the serial number:  
Press and release a button on the wireless key.  
OR  
24 INPUT S/N  
AXXX-XXXX  
L
1
Manually enter the 7-digit serial number printed on the devices label.  
Press [] to accept serial number. The system checks for a duplicate.  
If a duplicate exists, a long error beep will sound and the serial number reverts back to all Xs allowing  
you to re-enter the serial number.  
Use the [A] key to move forward within the screen, and the [B] key to back up.  
If you entered YES previously at the SET TO CONFIRM prompt (see first prompt following entry into the  
Expert Programming Mode), the display on the left appears.  
To confirm, activate the button on the wireless key that corresponds to this zone.  
XMIT TO CONFIRM  
PRESS TO SKIP  
If the serial number transmitted does not match the serial number entered, a display similar to the one  
at the left appears.  
If so, activate the loop input or button on the transmitter once again. If a match is not obtained (i.e., summary  
display does not appear), press the [#] key and then enter the correct serial number.  
Entd  
A022-4063  
A022-4064  
Rcvd  
Activate the button on the wireless key again after re-entering the serial number.  
If the serial number transmitted matches the serial number entered, the system will beep 3 times and  
revert to the "Start Zone No." prompt and will show the lowest numbered zone of the next available 4-zone  
group (4 consecutive zones) that is available for programming.  
ENTER ZONE NO  
00 = QUIT  
28  
After all the wireless keys have been entered, enter 000 for the zone number to quit.  
After you have enrolled each wireless device, remove ONE of the serial number labels from that device and affix it in  
the appropriate column on the worksheets provided later in this Programming Guide; then enter the other information  
(zone number, zone type, etc.) relevant to that device.  
18 –  
 
Wireless Key Default Templates  
5804  
5804BD  
Template 1  
Loop Function  
Zone Type Template 4  
Loop  
Function  
Zone Type  
1
No Response  
23  
1
No Response  
No Response  
Arm AWAY  
Disarming  
23  
2
3
4
Disarming  
22  
2
23  
Arm AWAY  
No Response  
21  
3
21  
23  
4
22  
Template 2  
Template 3  
Loop Function  
Zone Type Template 5  
Loop  
1
Function  
Zone Type  
1
2
3
4
No Response  
23  
No Response  
Arm STAY  
Arm AWAY  
Disarming  
23  
Disarming  
Arm AWAY  
Arm STAY  
22  
2
20  
21  
3
21  
20  
4
22  
Loop Function  
Zone Type Template 6  
Loop  
Function  
Zone Type  
1
2
3
4
24-Hour Panic  
07  
22  
21  
20  
1
2
3
4
24-Hour Panic  
Arm STAY  
Arm AWAY  
Disarming  
07  
20  
21  
22  
Disarming  
Arm AWAY  
Arm STAY  
19 –  
 
Alpha Descriptors Programming  
You can program a user-friendly English language description/location for all protection zones, relays, keypad panics, polling  
loop short, and RF receiver supervision troubles.  
Each description can be composed of a combination of words (up to 3) that are selected from a vocabulary of 244 words  
stored in memory, and any word can have an "s" or " s " added to it.  
NOTE: Due to the use of 2-digit zone numbers, the first word of the descriptor is limited to 7 characters if you want it to fit on  
the top line of the display.  
In addition, up to 20 installer-defined words can be added to those already in memory. Thus, when an alarm or trouble occurs  
in a zone, an appropriate description for the location of that zone will be displayed at the keypad.  
A custom installers message can be programmed for each partition that is displayed when the system is "Ready" (e.g., THE  
PETERSONS).  
1. To program alpha descriptors, enter Programming mode, then press #93 to display "ZONE PROG?"  
2. Press [0] (NO) twice to display "ALPHA PROG?".  
3. Press [1] to enter Alpha Programming.  
There are 5 submenu selections that will be displayed one at a time.  
Press [1] to select the mode desired.  
Press [0] to display the next mode available. The alpha menu selections are:  
ZONE DESCRIP?  
DEFAULT SCREEN?  
CUSTOM WORD?  
PART DESCRIP?  
EXIT EDIT MODE?  
For entering zone descriptors.  
For creating custom message; displayed when system is ready.  
For creating custom words for use in descriptors.  
For creating 4-character partition names.  
Press [1] to exit back to #93 Menu Mode.  
4. Refer to the sections that follow for procedures for adding alpha descriptors.  
Zone Descriptors  
1. Select ZONE DESCRIPTOR mode.  
The keypad keys perform the following functions:  
[3] Scrolls both alphabet and actual words in ascending alphabetical order.  
[1] Scrolls both alphabet and actual words in descending alphabetical order.  
[2] Adds or removes an "s" or " 's " to a vocabulary word.  
[6] Switches between alphabet and actual word list; used to accept entries.  
[8] Saves the zone description in the system's memory.  
[#] [#] plus zone number displays the description for that zone.  
2. Enter the zone number to which you want to assign a descriptor.  
For example, key [] 01 to begin entering the description for Zone 1, (key [] 02 for Zone 2, [] 03 for Zone 3, etc.). The  
following is displayed: ZN 01 A.  
Note that the first letter of the alphabet appears after the zone number, and that the zone number is automatically  
included with the description.  
3. Enter the descriptor for that zone.  
Use one of two methods as follows:  
(Assume, for example, that the desired description for Zone 1 is BACK DOOR.)  
a) Press [#] followed by the 3-digit number of the first word from the fixed dictionary shown later in this section (e.g.,  
[0][1][3] for BACK).  
Press [6] in order to accept the word and proceed, or press [8] to store the complete descriptor and exit;  
or  
b) Select the first letter of the desired description (note that "A" is already displayed). Use the [3] key to advance  
through the alphabet and the [1] key to go backward.  
Press [3] key repeatedly until "B" appears (press [1] to go backwards if you happen to pass it), then press [6] to  
display the first available word beginning with B.  
Press [3] repeatedly to advance through the available words until the word BACKis displayed.  
To add an "s" or " 's," if you need to, press 2. The first depression adds an "s," the second depression adds  
an " 's, " the third depression displays no character (to erase the character), the fourth depression adds an  
"s," etc.  
20 –  
 
4. Accept the word.  
To accept the word, press [6], which switches back to the alphabet list for the next word, or press [8] to store the  
complete descriptor and then exit.  
5. Select the next word.  
For selection of the next word (DOOR), repeat step 3a (word #057) or 3b, but selecting the word "DOOR.”  
To accept the word, press [6], which again switches back to alphabet list.  
6. Store the descriptor.  
When all desired words have been entered, press [8] to store the description in memory.  
To review the zone descriptors, key [#] plus zone number (e.g., #01).  
To edit zone descriptors, key [] plus zone number (e.g., 01)  
7. Exit Zone Description Mode: enter 00.  
Default Screen (Custom Message Display)  
Normally, when the system is in the disarmed state, the following display is present on the keypad.  
****DISARMED****  
READY TO ARM  
Part or all of the above message can be modified to create a custom installer message for each partition. For example,  
****DISARMED****on the first line or READY TO ARMon the second line could be replaced by the installation company  
name or phone number for service.  
Note: There are only 16 character spaces on each of the two lines.  
To create a custom display message, proceed as follows:  
1. Select Default Screen mode.  
The keypad asks for the partition number for this message.  
Enter the partition number. Press [] to accept entry.  
The following display appears:  
****DISARMED****  
READY TO ARM  
A cursor is present at the extreme left of the first line (over the first "star"). Press [6] to move the cursor to the right and [4]  
to move the cursor to the left. Press [7] to insert spaces or erase existing characters.  
2. Create the message.  
For example, to replace READY TO ARMwith the message SERVICE 424-0177,proceed as follows:  
Press [6] to move the cursor to the right, and continue until the cursor is positioned over the first location on the second  
line.  
Press [3] to advance through the alphabet to the first desired character (in this case, "S"). Press [1] to go backward, when  
necessary. When the desired character is reached, press [6].  
The cursor then moves to the next position, ready for entry of the next character (in this example, "E"). When the cursor  
reaches a position over an existing character, press [3] or [1] to advance or back up from that character in the alphabet.  
Proceed in this manner until all characters in the message have been entered.  
3. Save the message.  
Store the new display message in memory by pressing [8].  
4. The system asks for a new partition number.  
Enter 0 to quit or 1-8 for a new partition number.  
Custom Words  
Up to 20 installer-defined words can be added to the built-in vocabulary. Each of the 20 "words" can actually consist of several  
words, but bear in mind that a maximum of 10 characters can be used for each word string.  
1. Select CUSTOM WORD Mode.  
The keys perform the following functions:  
[3] Advances through alphabet in ascending order.  
[1] Advances through alphabet in descending order.  
[6] Selects desired letter; moves the cursor 1 space to the right.  
[4] Moves the cursor one space to the left.  
[7] Inserts a space at the cursor location, erasing any character at that location.  
[8] Saves the new word in the system's memory.  
[] Returns to Description Entry Mode.  
21 –  
 
2. Enter the custom word number (01-20) you want to create.  
For example, if you are creating the first word (or word string), enter 01; when creating the second word, enter 02, and so  
on. A cursor now appears at the beginning of the second line.  
3. Type the word using one of two methods as follows:  
a) Press [#], followed by the 2-digit entry for the first letter you would like to display (e.g., 65 for "A").  
When the desired character appears, press [6] to select it. The cursor will then move to the right, in position for the  
next character. Press [#] plus the 2-digit entry for the next letter of the word.  
or  
b) Press 3 to advance through the list of symbols, numbers, and letters.  
Press 1 to move back through the list.  
When you have reached the desired character, press [6] to select it. The cursor then moves to the right, in position  
for the next character.  
4. Repeat step 3 to create the desired custom word (or words).  
Press [4] to move the cursor to the left if necessary.  
Press [7] to enter a blank (or to erase an existing character).  
Each word or word string cannot exceed 10 characters.  
5. Save the word by pressing [8].  
This returns you to the CUSTOM WORD?display. The custom word (or string of words) is automatically added to the  
built-in vocabulary at the end of the group of words beginning with the same letter.  
Custom words are retrieved as word numbers 250 to 269 for words 1 to 20, respectively, when using method 3a to enter  
alpha descriptors.  
When using method 3b to enter alpha descriptors, each word appears at the end of the group of words that begin with the  
same letter as it does.  
6. Repeat steps 2 through 6 to create up to a maximum of 20 custom words (or word strings).  
7. Exit Custom Word Mode by entering 00 at the CUSTOM WORDprompt.  
Partition Descriptors  
1. Select "Part DESCRIPT." Mode.  
The system asks for the partition number desired. Enter the number as a single-key entry 1-8.  
2. Follow the same procedure as for custom words.  
Note: The partition descriptors are limited to 4 characters (e.g., WHSE for warehouse).  
22 –  
 
Alpha Descriptor Vocabulary  
(For entering alpha descriptors. To select a word, press [#] followed by the words 3-digit number.)  
NOTE: This vocabulary is not to be used for relay voice descriptors. See the Relay Voice Descriptors section when  
programming relay voice descriptors.  
000 (Word Space)  
001 AIR  
002 ALARM  
003 ALCOVE  
004 ALLEY  
005 AMBUSH  
006 AREA  
007 APARTMENT  
008 ART  
009 ATTIC  
010 AUDIO  
011 AUXILIARY  
102 INTERIOR  
103 INTRUSION  
151 POLICE  
152 POOL  
153 POWER  
203 TRAP  
052 DETECTOR  
053 DINING  
054 DISCRIMINATOR  
055 DISPLAY  
056 DOCK  
057 DOOR  
058 DORMER  
059 DOWN  
060 DOWNSTAIRS  
061 DRAWER  
062 DRIVEWAY  
063 DRUG  
204 ULTRA  
205 UP  
104 JEWELRY  
105 KITCHEN  
154 QUAD  
206 UPPER  
207 UPSTAIRS  
208 UTILITY  
209 VALVE  
210 VAULT  
211 VIBRATION  
212 VOLTAGE  
155 RADIO  
156 REAR  
106 LAUNDRY  
107 LEFT  
108 LEVEL  
109 LIBRARY  
110 LIGHT  
111 LINE  
112 LIQUOR  
113 LIVING  
114 LOADING  
115 LOCK  
157 RECREATION  
158 REFRIG  
159 REFRIGERATION  
160 RF  
161 RIGHT  
162 ROOM  
213 WALL  
214 WAREHOUSE  
215 WASH  
216 WEST  
217 WINDOW  
218 WINE  
219 WING  
220 WIRELESS  
221 WORK  
064 DUCT  
012 BABY  
013 BACK  
014 BAR  
015 BARN  
163 ROOF  
065 EAST  
066 ELECTRIC  
067 EMERGENCY  
068 ENTRY  
069 EQUIPMENT  
070 EXECUTIVE  
071 EXIT  
164 SAFE  
116 LOOP  
117 LOW  
118 LOWER  
165 SCREEN  
166 SENSOR  
167 SERVICE  
168 SHED  
169 SHOCK  
170 SHOP  
171 SHORT  
172 SHOW  
173 SIDE  
174 SKYLIGHT  
175 SLIDING  
176 SMOKE  
177 SONIC  
016 BASEMENT  
017 BATHROOM  
018 BED  
019 BEDROOM  
020 BELL  
021 BLOWER  
022 BOILER  
023 BOTTOM  
024 BOX  
025 BREAK  
026 BUILDING  
027 BURNER  
119 MACHINE  
120 MAGNETIC  
121 MAIDS  
122 MAIN  
123 MASTER  
124 MAT  
125 MEDICAL  
126 MEDICINE  
127 MICROWAVE  
128 MONEY  
129 MONITOR  
130 MOTHERS  
131 MOTION  
132 MOTOR  
133 MUD  
072 EXTERIOR  
222 XMITTER  
223 YARD  
073 FACTORY  
074 FAILURE  
075 FAMILY  
076 FATHERS  
077 FENCE  
078 FILE  
079 FIRE  
080 FLOOR  
081 FLOW  
224 ZONE (No.)  
225 ZONE  
226  
227  
0
1
178 SONS  
028 CABINET  
029 CALL  
030 CAMERA  
031 CAR  
032 CASE  
228 1ST  
229  
230 2ND  
231  
232 3RD  
233  
234 4TH  
235  
236 5TH  
237  
238 6TH  
239  
240 7TH  
241  
242 8TH  
243  
179 SOUTH  
180 SPRINKLER  
181 STAMP  
182 STATION  
183 STEREO  
184 STORE  
185 STORAGE  
186 STORY  
187 STRESS  
188 STRIKE  
189 SUMP  
2
082 FOIL  
083 FOYER  
084 FREEZER  
085 FRONT  
086 FUR  
3
033 CASH  
034 CCTV  
4
134 NORTH  
135 NURSERY  
035 CEILING  
036 CELLAR  
037 CENTRAL  
038 CIRCUIT  
039 CLIP  
040 CLOSED  
041 COIN  
042 COLD  
043 COATROOM  
044 COLLECTION  
045 COMBUSTION  
046 COMPUTER  
047 CONTACT  
087 FURNACE  
5
136 OFFICE  
137 OIL  
138 OPEN  
139 OPENING  
140 OUTSIDE  
141 OVERFLOW  
142 OVERHEAD  
088 GALLERY  
089 GARAGE  
090 GAS  
6
7
190 SUPERVISED  
191 SUPERVISION  
192 SWIMMING  
193 SWITCH  
091 GATE  
8
092 GLASS  
093 GUEST  
094 GUN  
9
244 9TH  
250 Custom Word 1  
194 TAMPER  
195 TAPE  
196 TELCO  
197 TELEPHONE  
198 TELLER  
199 TEMPERATURE  
200 THERMOSTAT  
201 TOOL  
143 PAINTING  
144 PANIC  
145 PASSIVE  
095 HALL  
096 HEAT  
097 HIGH  
098 HOLDUP  
099 HOUSE  
to  
269 Custom Word 20  
146 PATIO  
147 PERIMETER  
148 PHONE  
149 PHOTO  
150 POINT  
048 DAUGHTERS  
049 DELAYED  
050 DEN  
100 INFRARED  
101 INSIDE  
051 DESK  
202 TRANSMITTER  
CHARACTER (ASCII) CHART  
(For Adding Custom Words)  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
(space)  
!
"
#
$
%
&
(
)
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
*
+
,
-
.
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
4
5
6
7
8
9
:
62  
63  
64  
65  
66  
67  
68  
69  
70  
71  
>
?
72  
73  
74  
75  
76  
77  
78  
79  
80  
81  
H
I
J
K
L
M
N
O
P
Q
82  
83  
84  
85  
86  
87  
88  
89  
90  
R
S
T
U
V
W
X
Y
Z
@
A
B
C
D
E
F
/
0
1
2
3
;
<
=
G
Notes: This factory-provided vocabulary of words is subject to change.  
Bulleted words in bold face type are those that are also available for use by the 4285/4286 VIP Module. If you are  
using a VIP Module, and words other than these are selected for alpha descriptors, the Voice Module will not provide  
annunciation of those words.  
23 –  
 
Device Programming  
This menu is used to program keypads, receivers, and relay modules, etc.  
Device Address 00 is always set as an alpha keypad assigned to Partition 1 with no sounder suppression  
options, and these settings cannot be changed.  
From Data Field Programming mode, press #93 to display "ZONE PROG?" Press [0] repeatedly to display "DEVICE PROG?"  
PROMPT  
EXPLANATION  
Press [1] to enter Device Programming.  
DEVICE PROG?  
1=YES 0=NO  
0
The device address identifies the device to the control. Enter the 2-digit device address number to match  
the devices physical address setting (01-30).  
Press [] to accept entry.  
DEVICE ADDRESS  
01-30, 00=QUIT  
01  
Select the type of addressable device as follows:  
DEVICE TYPE  
00 = device not used  
03 = RF receiver (5881)  
00  
01 = alpha keypad (6139/6160)  
02 = fixed-word keypad (6137/6150)  
Press [] to accept entry.  
04 = output relay module (4204)  
05 = voice (VIP) Module (4285/4286)  
Alpha or Fixed-Word Keypad  
PROMPT  
EXPLANATION  
If you selected device type 01 (alpha keypad), or 02 (fixed-word keypad), this prompt appears. Enter the  
addressable devices default partition number (01 to maximum number of partitions programmed for system  
in field 2*00). This is the primary partition for the device. Enter 9 to make this keypad a "Master" keypad for  
the system.  
01 CONSOLE PART.  
1
Press [] to accept entry.  
Keypads can be individually programmed to suppress arm/disarm beeps, entry/exit beeps and chime mode  
beeps. This helps prevent unwanted sounds from disturbing users in other areas of the premises.  
Enter a number 00-03 for the keypad sounding suppression options desired for the keypad as follows:  
00 = no suppression  
01 SOUND OPTION  
00  
01 = suppress arm/disarm & entry/exit beeps  
02 = suppress chime mode beeps only  
03 = suppress arm/disarm, entry/exit and chime mode beeps  
Press [] to accept entry.  
RF Expander  
PROMPT  
EXPLANATION  
If you selected device type 03 (RF receiver), this prompt appears. Enter the 2-digit House ID (00-31). This  
is required if you are using a wireless keypad (5827/5827BD).  
01 RF EXPANDER  
HOUSE I  
00  
Press [] to accept entry.  
VIP Module  
PROMPT  
EXPLANATION  
If you selected device type 05 (VIP Module) this prompt appears. Enter the partition number 1-8 in which the  
module is located.  
Press [] to accept entry.  
01 MODULE PART.  
1
Press 00 + [] to exit Menu mode.  
Press 99 to exit Program mode.  
24 –  
 
Relay Programming  
The system supports up to 16 relays. Relays can be used to perform many different functions and actions. Each output must  
be programmed to begin one of three types of ACTIONS at a designated START event, and end that ACTION at a designated  
STOP event. The options used to start and stop these devices are described below, followed by the actual screen prompts  
and available entries.  
The letter(s) in parentheses after each function described below, such as (A) after ACTION, are those that appear in the  
various summary displays of programmed data during programming.  
ACTION (A)  
The "ACTION" of the device is how the device will respond when it is activated by the "START"  
programming. You may want the device to activate momentarily, to pulse on and off continuously, or to  
remain activated until some other event occurs to stop it. There are five different action choices:  
ACTIVATE for 2 SECONDS and then reset.  
ACTIVATE and REMAIN ACTIVATED until stopped by some other event.  
PULSE ON and OFF until stopped by some other event (do not use with an FSA device).  
NO RESPONSE when the device is not used.  
START (STT)  
The "START" programming determines when and under what conditions the device is activated. The  
following START options are available:  
1) EVENT (EV) is the condition (alarm, fault, trouble) that must occur to a zone or group of zones (zone  
list) in order to activate the device. These conditions apply only when a zone list is used. The different  
choices for "EVENT" are listed below and in Programming Relayslater in this section.  
ALARM  
Action begins upon any alarm in an assigned zone in the zone list.  
Action begins upon any opening of an assigned zone in the zone list.  
Action begins upon any trouble condition in an assigned zone in the zone list.  
Action is not dependent upon one of the above events.  
FAULT  
TROUBLE  
NOT USED  
ZONE LIST (ZL) is a group of zones to which the EVENTapplies in order to activate a particular  
device. Note that there are a total of 8 zone lists that can be programmed; when the selected EVENT  
(alarm, fault or trouble) occurs in any zone in the selected StartZONE LIST (1-8), activation of the  
selected device will START.  
2) ZONE TYPE/SYSTEM OPERATION (ZT). If all zones to be used to start the device have the same  
response type, and there are no other zones of this type that are not to activate this device, then  
ZONE TYPEmay be used instead of a "ZONE LIST" and "EVENTto activate the device.  
If a system operation, such as DISARMINGor ANY FIRE ALARM,is to activate the device, enter  
the appropriate choice under the ZONE TYPEoption.  
The “ZONE TYPE/SYSTEM OPERATION” option functions independently of the “EVENT/ZONE  
LIST” combination.  
If a specific "ZONE TYPE" is chosen, any zone of that response type going into alarm, trouble, or fault  
will cause the device to activate as selected in "ACTION.If the same ZONE TYPEis also chosen for  
the STOP programming, any zone of that type that restores will de-activate the device.  
If a "SYSTEM OPERATION" is chosen, that operation will cause the device to activate as selected in  
"ACTION.The different choices for "ZONE TYPE" and "SYSTEM OPERATION" are listed in  
Programming Relayslater in this section, and on the Programming Form.  
3) PARTITION NO. (P). The device's "Start" ZONE TYPE/SYSTEM OPERATION may be limited to an  
occurrence on one partition (1-8), or any partition (0).  
STOP (STP):  
The "STOP" programming determines when and under what conditions the device is de-activated. The  
following options are available:  
1). RESTORE ZONE LIST (ZL). If a "ZONE LIST" is used as the Stopevent, the device de-activates  
when all the zones in that list restore from a previous fault, trouble, or alarm condition. This occurs  
regardless of what is programmed to "START" the device; therefore, a "RESTORE ZONE LIST" is  
normally only used when a "ZONE LIST" is used to start the device.  
2). ZONE TYPE/SYSTEM OPERATION (ZT). Instead of using a "RESTORE ZONE LIST," you can select  
a specific zone (response) type or system operation action to de-activate the device.  
If you choose a specific "ZONE TYPE," any zone of that response type that restores from a previous  
alarm, trouble, or fault condition will cause the device to de-activate.  
If you choose a "SYSTEM OPERATION," that operation causes the device to de-activate. The  
different choices for "ZONE TYPE" and "SYSTEM OPERATION" are listed in Programming Relays”  
later in this section, and in the Programming Form.  
3) PARTITION NO. (P). The device's "Stop" Zone Type/System Operation may be limited to an  
occurrence on one partition (1-8), or on any partition (0).  
The ZONE TYPE/SYSTEM OPERATIONoption functions independently of the  
RESTORE/ZONE LISTcombination.  
25 –  
 
Relay Devices Programming  
From Data Field Programming Mode, press #93 to display the "ZONE PROG?" prompt. Press [0] (NO) to each menu option  
until the "RELAY PGM?" prompt appears. Press [1] (YES).  
While in this mode, press [] to advance to next screen. Press [#] to back up to the previous screen.  
PROMPT  
EXPLANATION  
Enter the relay (output device) identification number 01-16. This is a reference number only, used for  
identification purposes. The actual module address and relay number on the module are programmed in the  
last two prompts.  
ENTER RELAY #  
(00=QUIT)  
01  
Press [] to continue.  
Press [] to continue.  
02 A EV ZL ZT P  
STT 0 0 00 00 0  
The keypad displays a summary STOP screen.  
02  
A
0
ZL ZT  
00 00  
P
Press [] to continue.  
STOP  
0
The Relay Action is the way in which the relay will respond when activated by the "start" event. Enter the  
desired action for this relay as follows:  
0=not used; 1=close for 2 secs.; 2=stay closed; 3=pulse on/off  
02 RELAY ACTION  
NO RESPONSE  
0
0
An output may be activated by an Event/Zone List combination, and/or by a Zone Type/System Operation.  
For an Event/Zone List combination, enter the event code as follows:  
0=not used; 1=alarm; 2=fault; 3=trouble  
If you are not using a Zone List to activate the relay, enter 0.  
Press [] to continue.  
02 START EVENT  
NOT USED  
A zone list is a set of zones that can be used to initiate the start or stop relay action. If a zone list is being  
used to start this relay action, enter the zone list number, 1-8. If a zone list is not being used, enter 0.  
Press [] to continue.  
02 START: ZN LIST  
0
A Zone Type/System Operation can be used instead of or in addition to an Event/Zone List combination or  
a specific zone to start the relay action. If a Zone Type/System Operation is being used, enter the 2-digit  
code as listed in the table that follows.  
02 START: ZN TYPE  
NO RESPONSE  
00  
Press [] to continue.  
Choices for Start/Stop Zone Types and System Operations:  
00 = No Response (Not Used)  
01 = Entry/Exit #1  
02 = Entry/exit #2  
03 = Perimeter  
04 = Interior Follower  
05 = Trouble Day/Alarm Night  
06 = 24-Hr. Silent  
23 = No Alarm Response  
31 = End of Exit Time  
32 = Start of Entry Time  
33 = Any Burglary Alarm  
34 = Code + [#] + 71 Key Entry  
35 = Code + [#] + 72 Key Entry  
36 = At Bell Timeout **  
37 = 2 Times Bell Timeout **  
38 = Chime  
39 = Fire Alarm  
40 = Bypassing  
41 = AC Power Fail  
42 = System Battery Low  
43 = Communication failure  
44 = RF Low Battery  
45 = Polling Loop Failure  
51 = RF Receiver Failure  
52 = Kissoff  
54 = Fire Zone Reset  
55 = Disarm + 1 Minute  
56 = XX Minutes (enter XX in field 1*74) *  
57 = YY Seconds (enter YY in field 1*75) *  
58 = Duress  
60 = Audio Alarm Verification (must be  
selected for both START and STOP  
operation)  
07 = 24-Hr. Audible  
08 = 24-Hr. Auxiliary  
09 = Fire Alarm or Trouble  
10 = Interior W/Delay  
20 = Arming-STAY***  
21 = Arming-AWAY****  
22 = Disarming (Code + Off)  
Stop condition only  
*
** Or at disarming, whichever occurs earlier  
*** The output also activates when the partition is armed in the INSTANT mode  
**** The output also activates when the partition is armed in the MAXIMUM mode  
If you are using options 56 and/or 57 (usually as the STOP Zone Type), you must program data fields 1*74  
and 1*75 for the respective relay timeouts for minutes and seconds.  
26 –  
 
PROMPT  
EXPLANATION  
If the starting event will be limited to occurring on a specific partition, enter the partition number (1-8) in  
which the start event will occur. Enter 0 for any partition.  
Press [] to continue.  
02 START: PARTN  
ANY PARTITION  
0
Do not use a zone programmed with an RF Button (Input Type BR) to STOP a relay. The system will not de-  
activate the relay.  
PROMPT  
EXPLANATION  
If a zone list is being used to stop this relay action, enter the zone list number, 1-8. The restore of a zone  
on the zone list stops the relay. If a zone list is not being used, enter 0.  
Press [] to continue.  
02 STOP: ZN LIST  
0
If a Zone Type/System Operation is being used to stop the relay action, enter the 2-digit code listed in the  
Choices for Start/Stop System Operation chart.  
Press [] to continue.  
02 STOP: ZN TYPE  
NO RESPONSE  
00  
0
This is the partition to which the stop condition will be limited. Enter 0 for any partition. Enter 1-8 for specific  
partition number.  
Press [] to continue.  
02 STOP: PARTN  
ANY PARTITION  
Relays may be grouped for common activation by time-driven events (commands 06-10). Enter 0 (no group)  
or 1-8 for a specific group number.  
Press [] to continue.  
02 RELAY GROUP  
0
0
The system may have some devices that are not intended to be under end user control, such as relays  
activating fire doors or machinery. Enter 1 if the end user will be restricted from accessing this relay group.  
Press [] to continue.  
02 RESTRICTION  
1=YES 0=NO  
Enter 1 for (ECP) relay modules (4204). Enter 2 for X-10 devices.  
Press [] to continue.  
02 RELAY TYPE  
ECP  
1
00  
0
If you selected 1 (4204), enter the actual modules address (01-15) as set by its DIP switches.  
Press [] to continue.  
02 ECP ADDRESS  
Enter the specific relay number on that module (1-4).  
Press [] to continue.  
02 MODULE RELAY#  
The keypad will display the Start and Stop summary screens again.  
Press [] to continue.  
If you selected 2 for X-10 devices, enter the numerical equivalent of the House Code of the device, as  
follows:  
02 HOUSE CODE  
A
00  
00  
A=00  
B=01  
C=02  
D=03  
E=04  
F=05  
G=06  
H=07  
I=08  
J=09  
K=10  
L=11  
M=12  
N=13  
O=14  
P=15  
Enter the numerical unit code of the X-10 device (00-15).  
Press [] to continue.  
02 UNIT CODE  
The keypad displays the Start and Stop summary screens again.  
Press [] to continue.  
When all relays have been programmed, enter 00 at the "ENTER RELAY NO." prompt.  
27 –  
 
If you are defining a zone list, continue to the next section. If not, enter 00 + [] at the next two prompts. You will then be  
asked "Quit Menu Mode?" Enter 1 for "Yes," 0 for "No." Then enter 99 to exit programming completely.  
Zone List Programming  
After all relays have been programmed, upon entering 00 at the "ENTER RELAY NO." prompt, you are asked to enter a zone  
list. If a zone list number was used to start or stop a relay, you must define the zones belonging to that list as follows:  
PROMPT  
EXPLANATION  
Enter the zone list number 1-8. Enter 0 to quit.  
ENTER Zn LIST ?  
0=QUIT  
0
Using 2-digit entries, enter each zone to be included in this zone list. Press [] after you enter each zone  
number.  
When you have entered all zones, enter 00.  
Press [] to continue.  
01 ADD ZONE #  
00=QUIT  
00  
Enter 0 to save this zone list. Enter 1 to delete it.  
01 Del Zn LIST ?  
1=YES 0=NO  
0
0
Enter 1 to delete one or more zones in that zone list. Enter 0 if no changes are necessary. If you enter 1,  
the following screen appears; otherwise, the "Enter Zone LIST" prompt reappears.  
01 DEL ZONES ?  
1=YES 0=NO  
Enter each zone number to be deleted from the zone list, pressing [] after each number.  
01 Zn to DELETE ?  
00=QUIT  
00  
This display appears if you pressed 0 at the Enter Zone LISTprompt. Enter the zone list number that you  
wish to view.  
Press [] to continue.  
VIEW Zn LIST ?  
0=QUIT  
0
Press [] to scroll through all zones in that list. Enter 00 +[] to quit.  
Press [1] to exit Menu Mode.  
Press 99 to exit Program Mode.  
01 ASSIGNED ZONE  
00=QUIT  
00  
Relay Voice Descriptors  
If you are using the 4285/4286 VIP Module, voice descriptors can be programmed for the 16 outputs. These descriptors are  
announced by the voice module when you access the relays via the # 70 Relay Access Mode over the telephone.  
Each voice descriptor can consist of up to 3 words selected from the Relay Voice Descriptors and Custom Word Substitutes  
Vocabulary list (later in this section).  
The index numbers from this vocabulary list are to be used for relay voice descriptors only. For normal  
system voice annunciation (e.g., alarms, troubles, status), use the highlighted words in the alpha vocabulary  
list in the Alpha Programming part of this guide.  
To enter relay voice descriptors, do the following:  
1. From Data Field Programming mode, press #93 to display the "ZONE PROG?" prompt.  
2. Press [0] (NO) to each menu option until the "RLY VOICE DESCR?" prompt is displayed. Follow the instructions below.  
While in this mode, press [] to advance to next screen. Press [#] to back up to previous screen.  
PROMPT  
EXPLANATION  
Press [1] to program voice descriptors for relays.  
RLY VOICE DESCR?  
1=YES 0=NO  
0
Enter the 2-digit relay number (01-32) for the relay desired, or enter 00 to quit Relay Voice Descriptor  
Programming Mode.  
Press []  
ENTER RELAY NO.  
00=QUIT  
01  
28 –  
 
PROMPT  
EXPLANATION  
From the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list, enter the 3-digit index  
number for the first word of the relay descriptor phrase.  
01 ENTER DESC d1  
Press [] to accept entry.  
From the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list, enter the 3-digit index  
number for the second word of the relay descriptor phrase. If second word is not desired, press [000].  
Press [] to accept entry.  
01 ENTER DESC d2  
01 ENTER DESC d3  
From the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list, enter the 3-digit index  
number for the third word of the relay descriptor phrase. If third word is not desired, press [000].  
Press [] to accept entry. The ENTER RELAY NO.prompt appears. Enter the next relay number to be  
programmed. When you have programmed all output devices, enter 00 to quit.  
Enter 99 to exit Program Mode.  
Relay Voice Descriptors and Custom Word Substitutes Vocabulary  
Word  
Index  
Daughter's ................208  
Den...........................052  
Detector....................128  
Device ......................060  
Dim...........................163  
Dining .......................031  
Door..........................016  
Down ........................008  
Downstairs................184  
Driveway...................130  
Duct..........................131  
Front.........................087  
North........................ 146  
Not........................... 012  
Sixth.........................219  
Smoke......................024  
Son's........................223  
South........................155  
Stairs........................006  
Station......................156  
Storage.....................157  
Sun...........................154  
System.....................062  
Air ............................ 116  
Alarm ....................... 255  
And .......................... 067  
Apartment ................ 117  
Appliances ............... 161  
Area ......................... 118  
Attic.......................... 119  
Garage.....................023  
Gas ..........................138  
Glass........................139  
Off............................ 011  
Office....................... 147  
On............................ 058  
One.......................... 070  
Open........................ 148  
Outside.................... 210  
Hall...........................050  
Heat .........................010  
Baby......................... 120  
Back......................... 121  
Bar ........................... 122  
Basement................. 021  
Bathroom ................. 051  
Battery...................... 053  
Bed .......................... 092  
Bedroom .................. 015  
Blower...................... 123  
Boiler........................ 124  
Bright ....................... 162  
Building.................... 125  
Burglary.................... 039  
Inside .......................209  
Kitchen.....................022  
Panic ....................... 013  
Partition ................... 090  
Patio ........................ 149  
Phone...................... 061  
Power ...................... 063  
Pump....................... 166  
Temperature.............158  
Third.........................159  
Three........................072  
Tool..........................213  
Two ..........................071  
East ..........................132  
Eight .........................077  
Eighth .......................221  
Equipment ................133  
Exit ...........................004  
Laundry....................140  
Left...........................027  
Library......................141  
Light .........................019  
Living........................030  
Loading ....................142  
Lower .......................094  
Up ............................025  
Upper .......................187  
Upstairs....................183  
Utility ........................185  
Rear ........................ 088  
Right........................ 028  
Room....................... 018  
Factory .....................134  
Father's.....................211  
Fence .......................135  
Fifth ..........................218  
Fire...........................040  
First .........................136  
Five...........................074  
Floor .........................029  
Four..........................073  
Fourth.......................217  
Foyer ........................137  
Machine ...................143  
Master......................144  
Medical.....................014  
Mother's ...................212  
Motion ......................145  
's.............................. 007  
Second .................... 056  
Service..................... 150  
Seven ...................... 076  
Seventh ................... 220  
Shed........................ 151  
Shop........................ 152  
West.........................215  
Window ....................017  
Wing.........................216  
Call........................... 009  
Central ..................... 089  
Chime ...................... 054  
Closed...................... 126  
Computer ................. 127  
Console.................... 066  
Zero..........................069  
Zone.........................002  
Nine..........................078  
Ninth.........................222  
Word  
Index  
Word  
Index  
Word  
Index  
Side ......................... 153  
Six ........................... 075  
Word  
Index  
No ............................165  
29 –  
 
Custom Word Substitutes for VIP Module Annunciation  
A substitute word can be programmed for each of the 20 custom words used in your alpha zone descriptions. The VIP Module  
announces this substitute word in place of the custom word that is displayed on the alpha keypad. For example, an alarm  
display of "Johns Bedroom" could be announced as "Sons Bedroom," as there is no annunciation for the custom word "John."  
Note that if a substitute word is not assigned, the VIP Module will not annunciate the zone descriptor at all, but will only  
annunciate the zone number.  
To enter custom word substitutes, do the following:  
1. From Data Field Programming Mode, press #93 to display the "ZONE PROG?" prompt.  
2. Press [0] (NO) to each menu option until the "CUSTOM INDEX ?" prompt is displayed.  
PROMPT  
EXPLANATION  
Enter [1] at this prompt.  
CUSTOM INDEX ?  
1=YES 0=NO  
0
Enter the custom word number (01-20) for which a voice substitute is desired. Enter 00 to quit this  
Programming Mode.  
CUSTOM WORD NO.  
00=QUIT  
Press [] to accept entry.  
Enter the 3-digit substitute word index number from the Relay Voice Descriptors and Custom Word  
Substitutes Vocabulary list in the Relay Voice Descriptors part of this section.  
01 ENTER INDEX #  
Press [] to accept entry.  
The "CUSTOM WORD NO." prompt is displayed. Enter the next custom word number to be substituted, or  
enter 00 to quit.  
30 –  
 
System Layout Worksheets  
Before programming any security system, you should first define the installation. To help you lay out a partitioned  
system, use the following worksheets. This will further simplify the programming process.  
PARTITIONS  
Descriptor  
(4-char max)  
Prim.  
Sub. #  
Sec.  
Sub. #  
Alpha Default Message  
(32-character maximum)  
Partition #  
Partition 1  
Partition 2  
Partition 3  
Partition 4  
Partition 5  
Partition 6  
Partition 7  
Partition 8  
Keyswitch Arming Partition Assignment (1-8):  
Wireless Keypad Partition Assignment (1-8):  
Voice Module Partition Assignment (1-8):  
Use Partition Descriptor (yes/no)?  
Common Lobby Partition Assignment (1-8):  
COMMUNICATION OPTIONS BY PARTITION  
Part. 1 Part. 2 Part. 3 Part. 4  
Option  
Part. 5 Part. 6  
Part. 7  
Part. 8  
Swinger Suppression Count 00-15; 00=no suppression  
Cancel Report After Disarm  
Dialer Reports for Panic (* + 1)  
Dialer Reports for Panic (# + 3)  
Dialer Reports for Panic (* + #)  
Dialer Reports for Duress  
Burglary Alarm Communications Delay (16 sec.)  
SYSTEM DEFINITIONS BY PARTITION (enter values or yes/no)  
Part. 1 Part. 2 Part. 3 Part. 4 Part. 5 Part. 6  
Option  
Part. 7  
Part. 8  
Entry Delay #1 (00, 30-225 seconds):  
Exit Delay #1 (00, 45-225 seconds):  
Entry Delay #2 (00, 30-225 seconds):  
Exit Delay #2 (00, 45-225 seconds):  
Quick Arming  
Multiple Alarms per Arming  
Console Panic for Zone 95 (* + 1)  
Console Panic for Zone 96 (# + 3)  
Console Panic for Zone 99 (* + #)  
Allow Sign-on (GOTO function)  
Non-Bypassable Zone*  
Sounder Timeout Duration for Bell (2 min. increments)  
Console Annunciation During Entry**  
Console Annunciation During Exit  
Confirmation of Arming Ding for Bell  
Chime on Bell  
Access Control Relay (field 1*76)  
Affects Lobby (check partitions that apply)  
Arms Lobby (check partitions that apply)  
*Can be any zone 01-86. **no= 3 beeps  
yes=continuous  
31 –  
 
PRINTER OPTIONS  
12- or 24-hour Time format  
EVENT LOG TYPES  
No  
Option  
Alarm  
Yes  
Printer On-Line (yes/no)  
1200 or 300 baud Printer Baud Rate  
Trouble  
Bypass  
Open/Close  
System  
DEVICES (keypads, 4204, rf receivers, vip module)  
Part Sound Opt House ID  
Addr  
00.  
01.  
02.  
03.  
04.  
05.  
06.  
07.  
08.  
09.  
10.  
11.  
12.  
13.  
14.  
15.  
16.  
17.  
18.  
19.  
20.  
21.  
22.  
23.  
24.  
25.  
26.  
27.  
28.  
29.  
30.  
Type  
Device Types:  
00 = Device Not Used  
01 = Alpha Keypad  
02 = Fixed-Word Keypad  
03 = RF Receiver  
04 = Output Relay Module  
05 = Voice Module  
NOTE:  
Address 04 must be used for the  
Voice Module, if used.  
Console Sounder Options:  
0 = No Suppression  
1 = Suppress Arm/Disarm and Entry/Exit Beeps  
2 = Suppress Chime Mode Beeps Only  
3 = Suppress Arm/Disarm, Entry/Exit and Chime  
Mode Beeps  
ACCESS CODES & USER DEFINITIONS FOR PARTITIONS 1 & 2  
4-digit  
Security  
Code  
Access  
Group  
0; 1-8  
Partition 1  
Open/  
Close  
Partition 2  
Open/  
Close  
2-Digit  
User #  
Auth.  
Level  
RF Key  
Global  
Arm  
2-Digit  
User #  
Auth.  
Level  
RF Key  
Global  
Arm  
32 –  
 
ACCESS CODES & USER DEFINITIONS FOR PARTITIONS 3 & 4  
4-digit  
Security  
Code  
Access  
Group  
0; 1-8  
Partition 3  
Open/  
Close  
Partition 4  
Open/  
Close  
2-Digit  
User #  
Auth.  
Level  
RF Key  
Global  
Arm  
2-Digit  
User #  
Auth.  
Level  
RF Key  
RF Key  
RF Key  
Global  
Arm  
ACCESS CODES & USER DEFINITIONS FOR PARTITIONS 5 & 6  
4-digit  
Security  
Code  
Access  
Group  
0; 1-8  
Partition 5  
Open/  
Close  
Partition 6  
Open/  
Close  
2-Digit  
User #  
Auth.  
Level  
RF Key  
Global  
Arm  
2-Digit  
User #  
Auth.  
Level  
Global  
Arm  
ACCESS CODES & USER DEFINITIONS FOR PARTITIONS 7 & 8  
4-digit  
Security  
Code  
Access  
Group  
0; 1-8  
Partition 7  
Open/  
Close  
Partition 8  
Open/  
Close  
2-Digit  
User #  
Auth.  
Level  
RF Key  
Global  
Arm  
2-Digit  
User #  
Auth.  
Level  
Global  
Arm  
Authority Levels:1=Master (arm, disarm, bypass, and/or modify lower level users)  
2=Manager (arm, disarm, bypass, and/or modify lower level users)  
3=Operator A (arm, disarm, bypass)  
4=Operator B (arm, disarm)  
5=Operator C (arm, disarm only if system was armed with this code)  
6=Duress code (arm, disarm, triggers silent panic alarm)  
33 —  
 
34 —  
 
35 —  
 
36 —  
 
37 —  
 
ZONE DEFINITIONS FOR KEYPAD PANIC ZONES 95, 96, & 99  
Enter yes/no for each partition-field *22  
Zone  
No.  
Zone  
Type  
Report  
Code  
Zone Information (part numbers) &  
Alpha Descriptor (3 words max.)  
1
2
3
4
5
6
7
8
95  
96  
99  
ZONE DEFINITIONS FOR SYSTEM ZONES; 88; 89, 90, 91, 97 & 98  
Zone Information (part numbers)  
Zone  
No.  
Zone Report  
Type Code  
&
Alpha Descriptor (3 words max.)  
88  
89  
90  
91  
97  
98  
Zone Types:  
00=zone not used  
01=entry/exit 1  
02=entry/exit 2  
03=perimeter  
05=day/night burglary  
06=24-hour silent  
07=24-hour audible  
08=24-hour auxiliary  
09=supervised fire  
10=interior (delay)  
20=arm stay  
21=arm away  
22=disarm  
23=no alarm response  
04=interior (follower)  
Input Types:  
00=not used  
05=RF button transmitter  
01=hardwired  
03=supervised RF transmitter  
04=unsupervised RF transmitter  
06=serial number polling loop  
07=Dip switch-type polling loop  
08=right loop dip switch polling loop  
38 —  
 
Relay Devices Worksheets  
Applicable only if relays (4204), or X-10 devices are used.  
Relays are programmed in the #93 Menu Mode in the Relay Programming Section. Fill in the required data on the  
worksheet below and follow the procedure in the Installation and Setup Guide as you enter the data during the displays  
and prompts that appear in sequence.  
Notes: 1. For 4204 the Device Programming section must be programmed for the device address. Set the DIP  
switches on the device for that address.  
2. For X-10 devices, use the 1361X10 transformer in place of the transformer that comes in the box with the  
control panel.  
S T A R T  
EV/ZL ZT / P  
S T O P  
ZL ZT / P  
Relay # for  
4204 or  
Unit Code for  
X-10  
Dev Add 4204  
or House Code  
for X-10  
OUTPUT  
DEV #  
Relay  
Group  
1=4204  
2=X-10  
A
Restrict  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
9.  
10.  
11.  
12.  
13.  
14.  
15.  
16.  
A =  
EV = EVENT  
ZL = ZONE LIST  
DEVICE ACTION  
0 = No Response; 1 = Close for 2 sec; 2 = Close and stay closed; 3 = Pulse on and off  
0 = Not used; 1 = Alarm; 2 = Fault; 3 = Trouble; 4 = Restore  
1-8, 0 = Not Used  
"START" ZONE LIST: Upon alarm, fault, trouble or restore of ANY zone in this list, device  
action will START.  
"STOP" ZONE LIST:  
Upon restore of ALL zones on this list, device action will STOP. It  
need not be same list as used for START.  
39 —  
 
ZT = ZONE TYPE/SYSTEM OPERATION  
Choices for Start/Stop Zone Types and System Operations:  
00 = No Response (Not Used)  
01 = Entry/Exit #1  
02 = Entry/exit #2  
03 = Perimeter  
04 = Interior Follower  
05 = Trouble Day/Alarm Night  
06 = 24-Hr. Silent  
23 = No Alarm Response  
31 = End of Exit Time  
32 = Start of Entry Time  
33 = Any Burglary Alarm  
34 = Code + [#] + 71 Key Entry  
35 = Code + [#] + 72 Key Entry  
36 = At Bell Timeout **  
37 = 2 Times Bell Timeout **  
38 = Chime  
43 = Communication failure  
44 = RF Low Battery  
45 = Polling Loop Failure  
51 = RF Receiver Failure  
52 = Kissoff  
54 = Fire Zone Reset  
55 = Disarm + 1 Minute  
56 = XX Minutes (enter XX in field 1*74) *  
57 = YY Seconds (enter YY in field 1*75) *  
58 = Duress  
60 = Audio Alarm Verification (must be  
selected for both START and STOP  
operation)  
07 = 24-Hr. Audible  
08 = 24-Hr. Auxiliary  
09 = Fire Alarm or Trouble  
10 = Interior W/Delay  
20 = Arming-STAY***  
21 = Arming-AWAY****  
22 = Disarming (Code + Off)  
39 = Fire Alarm  
40 = Bypassing  
41 = AC Power Fail  
42 = System Battery Low  
NOTE: Any zone in "ZT" for Start, going into alarm, fault, or trouble will activate the relay.  
Any zone in "ZT" for Stop, that restores will stop the relay action.  
*
Stop condition only  
** Or at Disarming, whichever occurs earlier  
*** The output also activates when the partition is armed in the INSTANT mode  
**** The output also activates when the partition is armed in the MAXIMUM mode  
P =  
PARTITION No. 1-8, 0 = Any  
ZONE LISTS FOR OUTPUT DEVICES Programmed in the #93 Menu Mode in the Output Programming Section. Fill in the  
required data on the worksheet below and follow the procedure shown earlier in this Programming Guide as you enter the  
data during the displays and prompts that appear in sequence. Up to 8 zone lists may be created  
Note: Record desired zone numbers below. More or fewer boxes than shown may be needed, as any list may include any or  
all of system's zone numbers.  
Zone List 1: Started or stopped by zone numbers (enter 00 to end entries).  
Zone List 2: Started or stopped by zone numbers (enter 000 to end entries).  
Zone List 3: Started or stopped by zone numbers (enter 000 to end entries).  
Zone List 4: Started or stopped by zone numbers (enter 000 to end entries).  
Zone List 5: Started or stopped by zone numbers (enter 00 to end entries).  
Zone List 6: Started or stopped by zone numbers (enter 000 to end entries).  
40 —  
 
Zone List 7: Started or stopped by zone numbers (enter 000 to end entries).  
Zone List 8: Started or stopped by zone numbers (enter 000 to end entries).  
Scheduling Menu Prompts  
To program schedules, enter Scheduling program mode by pressing [User Code] + # + 80 to display the first choice of the  
menu driven programming functions. NOTE: Only users with an Installer or Master level user code may enter the #80 mode.  
Press 0 (NO) or 1 (YES) in response to the displayed menu selection. Pressing 0 will display the next choice in sequence.  
Menu selections are as follows:  
PROMPT  
EXPLANATION  
For defining up to 20 time windows each with a start and a stop time programmed by entering the hours and  
minutes.  
Time Window ?  
1 = YES 0 = NO  
0
0
0
0
For defining the daily open and close schedules for the 8 partitions. Each partition can be programmed with  
an opening and closing window for each day of the week and holidays.  
O/C Schedules ?  
1 = YES 0 = NO  
For defining up to 16 holidays for which partitions they apply.  
Holidays ?  
1 = YES 0 = NO  
For defining up to 20 time driven events with the following parameters:  
Timed Events ?  
1 = YES 0 = NO  
Time window  
Action desired  
Action specifier  
Activation time  
Days of the week  
For defining the limitation of access schedules for the user codes. Each schedule can be programmed with  
two window for each day of the week and holidays  
Access Sched. ?  
1 = YES 0 = NO  
0
#80 & #81 MENU MODE KEY COMMANDS  
The following is a list of commands used while in the Menu mode.  
#80 or #81  
Enters Menu mode  
[ ]  
[#]  
Serves as ENTER key. Press to have keypad accept entry.  
Backs up to previous screen.  
0
Press to answer NO.  
1
Press to answer YES.  
01-09  
00  
All data entries are either 2-digit entries.  
Exits Menu mode, returns to normal operation mode when entered at the first question for each category.  
41 —  
 
Scheduling Worksheets  
Time Windows Definitions Worksheet. The system provides 20 time windows that are defined with start and stop times.  
They are programmed in the #80 Menu Mode. Fill in the required data on the worksheet below and follow the procedure in  
the installation instructions as you enter the data during the displays and prompts that appear in sequence.  
Time Window  
Number  
Start Time  
(HH:MM)  
Stop Time  
(HH:MM)  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
(Keep this worksheet handy, as you will be asked for a given time window number later in this section).  
Because the time windows are shared among all partitions, it is important to make sure that  
changing a time window does not adversely affect desired actions in other partitions.  
Daily Open/Close Schedule Worksheet: Using the time windows previously defined, fill in the required data on the  
worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and  
prompts that appear in sequence.  
Part  
Mon  
Op Cl  
Tues  
Op Cl  
Wed  
Op Cl  
Thur  
Op Cl  
Fri  
Sat  
Op  
Sun  
Op Cl  
Hol  
Op Cl  
Op  
Cl  
Cl  
1
2
3
4
5
6
7
8
42 —  
 
Holiday Schedule Worksheet: The system provides up to 16 holidays that can be assigned for the system. Each holiday  
can be assigned to any combination of partitions. Fill in the required data on the worksheet below and follow the procedure in  
the installation instructions as you enter the data during the displays and prompts that appear in sequence.  
HOL  
Partition  
Month/Day  
1
2
3
4
5
6
7
8
1
2
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
Time-Driven Event Worksheet: The system provides up to 20 time-driven events that can be programmed for the system.  
Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data  
during the displays and prompts that appear in sequence.  
Sched  
Num.  
1
Time  
Day(s)  
Action  
Desired  
Action  
Specifier  
Activation  
Time  
Window M T W T  
F
S
S
H
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
43 —  
 
Below is a list of the "Action" codes (desired actions) used when programming time-driven events. Note that these codes are  
independent of the "relay codes" programmed during the #93 Menu ModeRelay Programming mode. If using Time Driven  
Events, the following menu items must first be programmed using #93 Menu Mode - Relay Programming:  
Enter Relay No. (reference identification number)  
ECP Address  
Relay No.  
House Code  
Unit Code  
(4204)  
(4204)  
(X-10)  
(X-10)  
Relay Group  
Restriction  
Relay Type  
(if applicable)  
(4204 or X-10)  
Relay commands:  
Action Specifier for commands 01-05 is Relay No.; Action Specifier for commands 06-10 is Relay Group No.  
01 = Relay On  
02 = Relay Off  
03 = Relay Close for 2 seconds  
05 = Relay Close YY seconds (field 1*75)  
07 = Relay Group Off  
04 = Relay Close XX minutes (field 1*74)  
06 = Relay Group On  
08 = Relay Group Close for 2 seconds  
10 = Relay Group Close YY seconds (field 1*75)  
09 = Relay Group Close XX minutes (field 1*74)  
Arm/Disarm commands:  
Action Specifier for commands 20-24 is Partition(s). Activation times 1 (Beginning), 2 (End), 3 (During) are the only valid  
choices for auto-arming and disarming functions.  
20 = Arm-Stay  
21 = Arm Away  
22 = Disarm  
23 = Force Arm Stay (Auto-bypass faulted zns)  
24 = Force Arm Away (Auto-bypass faulted zns)  
Bypass commands:  
Action Specifier for commands 30-31 is Zone List #, Activation times 1 (Beginning), 2 (End), 3 (During) are the only valid  
choices for bypass commands.  
30 = Auto bypass - Zone list  
31 = Auto unbypass - Zone list  
Open/Close Windows:  
Action Specifier for commands 40-41 is Partition(s), and for 42 is Access Group. Activation time 3 (During) are the only valid  
choices for these commands.  
40 = Enable Opening Window  
41 = Enable Closing Window  
42 = Enable Access Window  
Activation time:  
Refers to when the action is to take place relative to the time window.  
1 = Beginning of time window  
2 = End of time window  
3 = During time window active period only (On at beginning of window, off at end).  
4 = Beginning and end of time window  
Limitation of Access Worksheet The system provides up to 8 Access Schedules that can be programmed for the system.  
Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data  
during the displays and prompts that appear in sequence.  
Acc  
Mon  
Tues  
Wed  
Thurs  
Fri  
Sat  
Sun  
Hol  
Sch W1 W2 W1 W2 W1 W2 W1 W2 W1 W2 W1 W2 W1 W2 W1 W2  
1
2
3
4
5
6
7
8
44 —  
 
Temporary Schedule #81 Menu Mode. The system provides a Temporary Schedule for each partition. Enter the temporary  
scheduling mode by pressing [Installer Code] + [#] + [81]. Fill in the required data on the worksheet below and follow the  
procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.  
Partition/Windows  
Mon  
Tue  
Wed  
Thu  
Fri  
Sat  
Sun  
1
2
3
4
5
6
Disarm Window  
Start Time HH:MM  
Stop Time HH:MM  
Arm Window  
Start Time HH:MM  
Stop Time HH:MM  
Disarm Window  
Start Time HH:MM  
Stop Time HH:MM  
Arm Window  
Start Time HH:MM  
Stop Time HH:MM  
Disarm Window  
Start Time HH:MM  
Stop Time HH:MM  
Arm Window  
Start Time HH:MM  
Stop Time HH:MM  
Disarm Window  
Start Time HH:MM  
Stop Time HH:MM  
Arm Window  
Start Time HH:MM  
Stop Time HH:MM  
Disarm Window  
Start Time HH:MM  
Stop Time HH:MM  
Arm Window  
Start Time HH:MM  
Stop Time HH:MM  
Disarm Window  
Start Time HH:MM  
Stop Time HH:MM  
Arm Window  
Start Time HH:MM  
Stop Time HH:MM  
45 —  
 
Partition/Windows  
Mon  
Tue  
Wed  
Thu  
Fri  
Sat  
Sun  
7
Disarm Window  
Start Time HH:MM  
Stop Time HH:MM  
Arm Window  
Start Time HH:MM  
Stop Time HH:MM  
Disarm Window  
8
Start Time HH:MM  
Stop Time HH:MM  
Arm Window  
Start Time HH:MM  
Stop Time HH:MM  
46 —  
 
VISTA-50P/VISTA-50PUL Summary of Connections Diagram  
P O L L I N G L O O P  
( F a s t / N o r m a l ) L o o p  
P r o g r a m m a b l e R e s p o n s e  
B R E A K D E T E C T O R L O O P  
L A T C H I N G T Y P E G L A S S  
( A l s o s u p p o r t s N O / N C B u r g c o n t a c t s )  
D E T E C T O R L O O P  
2 - W I R E S M O K E  
D a t a o u t  
D a t a i n  
C O N N E C T I O N  
N O  
R E D ( + ) )  
B L K (  
47 —  
 
165 Eileen Way, Syosset, New York 11791  
Copyright © 2004 Honeywell International, Inc.  
¬9,67$ꢀꢁ3ꢂ359ꢃꢃlꢄ  
VISTA50P-PRV2 5/04 Rev. A  
 

Grizzly Saw G0588 G0591 User Manual
Harbor Freight Tools Dust Collector 45794 User Manual
Harman Kardon DVD Player DVD22B User Manual
Hasbro Robotics 83649 80402 User Manual
Heartland Bakeware Range 9200 7200 User Manual
Hotpoint Refrigerator HME35 User Manual
Hotpoint Ventilation Hood HD90X User Manual
HP Hewlett Packard Laptop V3000 User Manual
HP Hewlett Packard Network Router 359449 001 User Manual
Husky Air Compressor D28752 User Manual